| Plan Review Notes For Permit 05011403 |
| Permit Number |
05011403 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-03-04 00:00:00 | DENIED: | | | 1.PLEASE CLARIFY THE LOCATION OF THE | | | RETURN AIR FOR BEDROOM #2.THE | | | MECHANICAL PLAN REFLECTS ONLY ONE DOOR | | | INTO THE BED/BATH/CLOSET AREA, WHEREAS | | | PLAN SHEET A1.3.09 & A2.2.06 INDICATE AN | | | ADDITIONAL DOOR INTO THE BEDROOM AREA. | | | PLEASE CLARIFY. | | | | | | 2.PLEASE INDICATE EQUIPMENT SCHEDULE | | | WITH THE PLANS. | | | | | | 3.NO COMBUSTIBLES ALLOWED IN THE | | | MECHANICAL CLOSETS AS THE CLOSET APPEARS | | | TO BE A RETURN AIR PLENUM. | | | | | | 4.AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED PER 2001 | | | FBC(M)307.2.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|