 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE PROVIDE A CALCULATION
 INCLUDING ALL ADDED LOADS IMPOSED,ALL
 EXISTING LOADS AND THE EXISTING OR
 PROPOSED SERVICE SPECIFICATIONS PER
 215.15.
  
 2} PLEASE INDICATE THE CIRCUIT NUMBER(S)
 AND THE OCP FOR EACH ADDITIONAL CIRCUIT
  
 USED.
  
  
  