| Plan Review Notes For Permit 05011327 |
| Permit Number |
05011327 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-02-04 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2.)FBC TABLE 704.1 REQUIRES A 2 HR | | | SEPARATION BETWEEN EDUCATIONAL AND | | | BUSINESS OCCUPANCIES.IF YOU ARE | | | PROVIDING A 1 HR BASED ON AN EXCEPTIONM, | | | PLEASE MAKE THIS CLEAR ON THE PLAN | | | SHOWING SQUARE FOOTAGES. | | | | | | 3.)PROVIDE THE DIMENSION BETWEEN DOOR | | | X AND DOOR 1 TO SHOW COMPLIANCE WITH FBC | | | CHAPTER 11 FIGURE 26. | | | | | | 4.)PROVIDE THE DIMENSION AT DOOR 1 TO | | | SHOW COMPLIANCE WITH FBC CHAPTER 11 | | | FIGURE 25. | | | |
|