| 2005-02-08 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05011284 |
| | ADD: 6430 SPARROW HAWK DRIVE |
| | CONT: RIF GROUP |
| | TEL: (561)239-5790 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 1)FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | DISCREPANCY, BETWEEN, SHEETS A-4 & A-5, |
| | THE AREA OR ROOM LEADING FROM THE DEN/ |
| | BEDROOM# 2 TO THE EXTERIOR, THE |
| | ELEVATIONS SHOW A ROOFED OVER AREA, |
| | WHEREAAS A-5 INDICATES NO ROOF IN THIS |
| | AREA, CORRECT. |
| | |
| | 2) FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | SHEET A-4 VERSES A-5 AREA OR ROOM BY THE |
| | DEN/ BEDROOM# 2, A-4 ELEVATION SHOWS THE |
| | ROOF COVERING THIS AREA, A-5 ROOF |
| | FRAMING PLAN INDICATES THIS AREA BEING |
| | OPEN TO THE SKY. |
| | |
| | 3) FRONT DOOR INDICATES THIS DOOR TO |
| | HAVE GLAZING, DISCUSSED WITH CONTRACTOR |
| | OVER THE PHONE THIS DOOR SHALL BE SOLID |
| | CORE, WILL SUBMIT NEW PRODUCT APPROVALS |
| | INDICATING SUCH, ARCHITECT WILL ALSO |
| | REVISE FRONT DOOR TO INDICATE SOLID |
| | CORE/ NO GLAZING.THIS WILL ACCOMPLISH |
| | COMPLIANCE WITH:FBC 1005.4.5 |
| | (GLITCH AMENDMENTS JULY 1, 2003) |
| | REQUIRES AT LEAST ONE MEANS OF ESCAPE |
| | FROM A DWELLING WHEN SHUTTERED FOR |
| | IMPACT PROTECTION. THE MEANS OF ESCAPE |
| | SHALL BE WITHIN THE FIRST FLOOR OF THE |
| | DWELLING AND CAN NOT BE LOCATED IN A |
| | GARAGE. OCCUPANTS IN ANY PART OF THE |
| | DWELLING SHALL HAVE ACCESS TO IT WITHOUT |
| | HAVING TO PASS THROUGH A LOCKABLE DOOR |
| | NOT UNDER THEIR CONTROL. INDICATE HOW |
| | COMPLIANCE WILL BE ACHIEVED. |
| | |
| | 4) SPOKE TO CONTRACTOR, WILL COME IN |
| | UNDER A SEPERATE PERMIT FOR STORM |
| | SHUTTERS. STORM SHUTTERS TO COMPLY |
| | WITH: |
| | 4A) PROVIDE STORM PANEL INFORMATION WITH |
| | INSTALLATION SCHEDULE AND KEY PLAN WITH |
| | SPECIFIC ANCHORS AND MOUNTING TO BE USED |
| | FOR ALL NON-IMPACT GLAZING. |
| | FBC 1606.1.4. |
| | 4B)FL BLD CODE 2001 SECTION 103.6, |
| | 1606.1.4, 1707.4 & 3401.7.2.4. |
| | PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| | SCHEDULE SUMMARIZING & IDENTIFYING |
| | OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| | BAR REINFORCING REQUIREMENTS, WALL PRES- |
| | SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| | SUBMITTED AT TIME OF PERMIT APPLICATION |
| | TO FACILITATE PLAN REVIEW AND PERMIT |
| | ISSUANCE. |
| | |
| | BUILDING PLAN REVIEW |