| 2005-03-01 00:00:00 | ********* UNSAT 2ND REVIEW ********* | | | | | | PLEASE SEE SOME ITEMS FROM PREVIOUS | | | REVIEW STILL NEED TO BE ADDRESSED. | | | PLEASE ALSO SEE ONE NEW COMMENT. | | | | | | 1)NOTE: NOTE #1 NO, PLEASE SEE REDLINED | | | PLANS FOR ITEMS NOT CIRCUITED. | | | PLEASE SEE RESPONSE LETTER MENTIONS TO | | | SEE REVISED "A-1"?? | | | | | | 2)NOTE: NOTE #2 NO, PLEASE SEE 600.5 FOR | | | REQUIRED SIGN CIRCUIT. NO OTHER ITEMS | | | INCLUDING "SHOW WINDOW" RECEPTS ARE | | | PERMITTED ON SIGN CIRCUIT. | | | PLEASE SEE RESPONSE LTR MENTIONS TO SEE | | | A-1? | | | | | | 3)NOTE: NOTE #3, OK, PANELS HAVE BEEN | | | RE-LABLED ON PLANS. | | | | | | 4)NOTE: NOTE #4 OK. | | | | | | 5)NOTE: NOTE #5 OK. | | | | | | NEW NOTE: | | | | | | 1)NOTE: PLEASE SEE HAND WRITTEN ITEMS ON | | | PLANS WHICH ARE SIGNED, DATED AND SEALED | | | BY AN ARCH /ENG ARE NOT PERMITTED. | | | FS 481.221, 471.025 | | | | | | 2)NOTE: PLEASE SEE A NOTTICE TO FS | | | 553.80(2)(B) IS GIVEN AT THIS TIME, THIS | | | IS ONLY A NOTICE. | | | | | | | | | PLEASE SEE ONE SET OF PLANS HAVE THE | | | ABOVE ITEMS REDLINED FOR AREAS OF NOTES. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | INSERT ONLY NEW SHEETS INTO TWO COMPLETE | | | SETS FOR REVIEW AND STAMPING. |
|