Plan Review Notes
Plan Review Notes For Permit 05011231
Permit Number 05011231
Review Stop P
Sequence Number 1
Notes
Date Text
2005-02-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 1) PLANS SHALL BE ROUTED TO FDBR,
 DIVISION OF BUSINESS REGULATION, HOTEL
 AND RESTURANT DIVISION FOR REVIEW.
 RESUBMIT WITH EACH SET OF PLANS STAMPED,
 AND WORK SHEETS ATTACHED. SECTION
 101.4.7.
 2) GREASE INTERCEPTORS SHALL BE SIZED BY
 RODNEY COMPO, ENVIRONMENTAL COMPLIANCE,
 WASTE ORD. #2838-96. (561) 837-4074 OR
 FAX (561) 659-7458. SUBMIT WORK SHEET
 FORM MR. COMPO WITH PLANS WHEN
 RESUBMITTING.
 3) SHT P-1 FLOOR PLAN FOR GREASE PIPING
 SHOWS THE FIRST FLOOR DRAIN AS "WC-3"
 NOT "FD" PLEASE CORRELATE RISER DIAGRAM
 AND FLOOR PLAN.
 4) SHT P-1 FLOOR PLAN AND GREASE PIPING
 ISOMETRIC. FS-1, (INDIRECT WASTE FROM
 ITEM #7) AND FD-2 SHALL CONNECT TO THE
 VENTED DRAIN LINE SEPARATELY. SECTION
 912.2.4.
 5) SHT P-2 SECTION 606.1(4) FULL OPEN
 VALVES ARE REQUIRED ON THE TOP OV EVERY
 WATER DOWN-FEED PIPE.
 6) SHT P-2 THE FOLLOWING INFORMATION IS
 REQUIRED FOR GAS PLANS/PERMIT:
 A. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 I. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. THESE
 VALVES AND UNIONS SHALL BE SHOWN ON THE
 GAS RISER DIAGRAM.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]