2005-01-31 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05011231
 ADD:7785 S DIXIE HWY
 CONT:PLAN REVIEW/PALM BEACH 2000
 TEL: (954)927-4885
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
  
 1)PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) CORRECT ADDRESS ON PLANS, ELEVATIONS
 TO 7785 FOR THE UNIT NUMBER, THE SITE
 ADDRES IS 7719 S DIXIE.
  
 3) F102.1* FIRE DISTRICT, NO TYPE VI
 CONSTRUCTION IS ALLOWED IN THE FIRE
 DISTRICT. NO COMBUSTIBLE WALLS, SEE
 PARAPET WALLS, AND WALL SECTIONS OF
 TOWER.
 SHEET A-9 THROU A-12 INDICATE THE USE OF
  
 RIB LATH FASTENING AS PER NOTE# 2,
 CORRECT SEE:2504.2.2 INSTALLATION
 OF EXTERIOR LATHING AND FRAMING SHALL
 COMPLY WITH ASTM C-1063. COMPLY WITH
 VERTICAL & HORIZONTAL FASTENING FOR RIB
 LATH.
  
 4) SHEET A-13 DETAIL# 3, INDICATES THE
 USE OF VINYL SOFFIT VENT AT 2 5/8" WIDE
 STRIP. PROVIDE CALCULATION SHOWING
 COMPLIANCE WITH 2309.7.1. INDICATE HOW
 MUCH OF THE VENT IS OPEN PER FOOT.
  
 5) SHEET A-14 DETAILS 1&2 REVISE:
 1707.4.4.2 TAPERED BUCKS:
 SHALL EXTEND BEYOND THE INTERIOR FACE
 OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS SUPPORTED.
  
 6) SAME DETAILS AS LISTED ABOVE, THE
 COMMENT THAT THE TAPCON IS TO A MINIMUM
 OF 3" INTO CONCRETE CORRECT? THE TAPCON
 HAS TO TRAVEL A 1 1/4" THROUGH THE BLOCK
 SHELL BEFORE HITTING THE 3,000 PSI
 CONCRETE?
  
 7) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 WWW.FLORIDABUILDING.ORG
  
 8)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) SLIDING WINDOW UNIT
 B) ARCHED WINDOWS
 C) TRUSS ANCHORS
  
 9)STORM SHUTTERS FL BLD CODE 2001
 SECTION 103.6, 1606.1.4, 1707.4 &
 3401.7.2.4. PROCEDURES: 1(B) A COMPLETE
 INSTALLATION SCHEDULE SUMMARIZING &
 IDENTIFYING OPENING SIZES, STORY
 HEIGHTS, UNIT MARK NUMBERS, UNIT
 SPANS/WIDTHS, UNIT STORM BAR REINFORCING
 REQUIREMENTS, WALL PRES- SURE ZONES,
 SLAT TYPES, ETC., SHALL BE SUBMITTED AT
 TIME OF PERMIT APPLICATION TO FACILITATE
 PLAN REVIEW AND PERMIT ISSUANCE.
 HIGHLIGHT THE PRODUCT APPROVAL
 INDICATING THE TYPE OF DETAIL USED AND
 THE TYPE OF FASTENER WITH TYPE OF
 MATERIAL OF THE STRUCTURE.
  
 10) VALUE LOW ON THE PERMIT, CALCULATED
 VALUE IS $304,406.00.
  
 11)BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026