Plan Review Notes
Plan Review Notes For Permit 05011045
Permit Number 05011045
Review Stop P
Sequence Number 1
Notes
Date Text
2005-02-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SANITARY RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. THE FLOOR PLAN
 DOES NOT SHOW A WASH MACHINE. ALSO NO
 SINK IS SHOWN ON THE FLOOR PLAN FOR THE
 NEW ADDITION. PLEASE INDICATE WHERE THE
 WASH MACHINE AND THE SINK ARE LOCATED ON
 THE FLOOR PLAN. ONLY SHOW NEW WORK ON
 THE SANT. RISER DIAGRAM. SECTION
 104.2.1.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]