| 2005-02-19 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) ENGINEERS SHALL LEGIBLY INDICATE |
| | THEIR NAME, ADDRESS, AND LICENSE NUMBER |
| | ON EACH SHEET, AND IF PRACTICING THROUGH |
| | A DULY AUTHORIZED ENGINEERING BUSINESS, |
| | ENGINEERS SHALL LEGIBLY INDICATE THEIR |
| | NAME AND LICENSE NUMBER, AS WELL AS, THE |
| | NAME, ADDRESS, AND CERTIFICATE OF |
| | AUTHROIZATION NUMBER OF THE ENGINEERING |
| | BUSINESS ON EACH SHEET. FAC |
| | 61G15-23.002(2) & FS 471.025. - |
| | SIGNATURE REQUIRED - NO INITIALS PER |
| | FDPE,S RULING. |
| | 2) PERSONAL SIGNATURE OF THE ARCHITECT |
| | REQUIRED. G1G1-16.003 FS 481.2055 - THE |
| | FOLLOWING INFORMATION MISSING FROM |
| | REQUIRED TITLE BLOCK: 61G1-16.004 |
| | (2) FIRM LICENSE NUMBER |
| | (6) PRINTED NAME OF THE PERSON SEALING |
| | THE DOCUMENT. FS 481.219 (CERTIFICATE OF |
| | AUTHORIZATION). |
| | 3) SHT D1.0 IN THE REMOVAL OF ANY PART |
| | OF A DRAINAGE SYSTEM, DEAD ENDS SHALL BE |
| | PROHIBITED. SECTION 704.5. ALL DEMO'D |
| | PIPING SHALL NOT BE COVERED PRIOR TO |
| | INSPECTION. |
| | 4) THE FOLLOWING INFORMATION IS REQUIRED |
| | ON THE PLANS TO SHOW COMPLIANCE WITH |
| | SECTIONS 11-4.16, 11-4.19, & 11-4.22: |
| | A) CLEAR FLOOR SPACE W/C 11-4.16.2 |
| | (TURNING AREA IS NOT CLEAR FLOOR SPACE) |
| | B) FLUSH CONTROLS W/C (WIDE SIDE) |
| | 11-4.16.5. |
| | C) HEIGHT OF LAV (34") 11-4.19.2 |
| | 5) SUBMIT A DETAIL FOR THE DRINKING |
| | FOUNTAIN SHOWING COMPLIANCE WITH THE |
| | FOLLOWING: |
| | A) SPOUT HEIGHT 11-4.15.2 |
| | B) CLEARANCES/CLEAR FLOOR SPACE |
| | 11-4.15.5 |
| | 6) SHT M2.0 WATER RISER DIAGRAM, WATER |
| | HAMMER ARRESTOR SHALL BE LOCATED NEAR |
| | THE FIXTURES IN AN "EFFECTIVE RANGE" NOT |
| | IN THE CEILING AS SHOWN. PDI-WH 201 AND |
| | MANUF. INSTALLATION INSTRUCTIONS. |
| | 7) SHT M2.0 WATER HEATER DETAIL. |
| | EMERGENCY HEATER PAN DRAIN AND P&T VALVE |
| | DISCHARGE LINE SHALL DRAIN TO A HUB |
| | DRAIN OR A FLOOR SINK. FLOOR DRAINS ARE |
| | NOT AN APPROVED INDIRECT WASTE RECEPTOR. |
| | SECTIONS 802.3 & 802.3.2. |
| | |