Plan Review Notes
Plan Review Notes For Permit 05010919
Permit Number 05010919
Review Stop M
Sequence Number 1
Notes
Date Text
2005-01-31 00:00:00DENIED:
 1.DUCT SMOKE DETECTOR IS INDICATED ON
 THE RETURN AIR.PER 2001 FBC(M)606.2.1
 AND NFPA 90A6.4.2.1 (1), DUCT SMOKE
 DETECTORS SHALL BE INSTALLED IN THE
 SUPPLY AIR DUCT.
  
 2.NO COMBUSTIBLES ALLOWED ABOVE THE
 CEILING IN THE RETURN AIR PLENUM PER
 2001 FBC(M)602.2.1.
  
 3.PLEASE NOTE THE ENERGY CALCULATIONS
 SHOW MAXIMUM TONNAGE AS 0.PLEASE
 CLARIFY.
  
 4.SEE COMMENT #1 BY DEWEY PALMER,
 ELECTRICAL PLANS EXAMINER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719