| Plan Review Notes For Permit 05010919 |
| Permit Number |
05010919 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-01-31 00:00:00 | DENIED: | | | 1.DUCT SMOKE DETECTOR IS INDICATED ON | | | THE RETURN AIR.PER 2001 FBC(M)606.2.1 | | | AND NFPA 90A6.4.2.1 (1), DUCT SMOKE | | | DETECTORS SHALL BE INSTALLED IN THE | | | SUPPLY AIR DUCT. | | | | | | 2.NO COMBUSTIBLES ALLOWED ABOVE THE | | | CEILING IN THE RETURN AIR PLENUM PER | | | 2001 FBC(M)602.2.1. | | | | | | 3.PLEASE NOTE THE ENERGY CALCULATIONS | | | SHOW MAXIMUM TONNAGE AS 0.PLEASE | | | CLARIFY. | | | | | | 4.SEE COMMENT #1 BY DEWEY PALMER, | | | ELECTRICAL PLANS EXAMINER. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719 |
|