| Notes |
| Date |
Text |
| 2005-02-08 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT A-1 SHOW TURNING AREA IN EACH | | | TOILET ROOMS DETAIL #2. SECTION | | | 11-4.22.3. | | | 2) SHT A-1 SHOW CLEAR FLOOR SPACE FOR | | | THE LOUNGE SINK. SECTION 11-4.24.5. | | | (FORWARD APPROACH REQUIRED, MAXIMUM 19" | | | UNDERNEATH THE SINK). | | | 3) SHT A-3 DETAIL #7 FLUSH CONTROLS TO | | | BE MOUNTED ON THE WIDE SIDE OF THE | | | TOILET AREA. SECTION 11-4.16.5. - DETAIL | | | #10 MAXIMUM SINK DEPTH TO BE 6-1/2". | | | SECTION 11-4.24.4. (MAX. 7" SHOWN). | | | 4) SUBMIT A DETAIL FOR THE DRINKING | | | SHOWING COMPLIANCE WITH 11-4.15 AND ALL | | | SUBSECTIONS. | | | 5) SHT P0.1 PLUMBING FIXTURE SCHEDULE. | | | SUBMIT MANUF. SPECIFICATION SHEETS FOR | | | THE POWERSTREAM RP-1 TANKLESS WATER | | | HEATER. SHEETS SHALL SHOW LISTING, AND | | | INSTALLATION INSTRUCTIONS. SECTION | | | 303.4 | | | 6) SHT P5.1 WATER RISER DIAGRAM, WATER | | | HAMMER ARRESTORS SHALL BE LOCATED IN AN | | | "EFFECTIVE RANGE" NEXT TO THE FIXTURES, | | | NOT IN THE CEILING AS SHOWN. PDI-WH 201 | | | AND MANUF INSTALL. INSTRUCTIONS. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|