| Plan Review Notes For Permit 05010848 |
| Permit Number |
05010848 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-02-08 00:00:00 | 1. PLEASE EXPLAIN NOTE ON A.1 "FIRE | | | SPRINKLER SYSTEM MONITOR". WHAT IS THIS | | | PROPOSED PANEL MONITORING WHICH | | | BUILDING | | | OR AREA. PLEASE EXPLAIN. | | | | | | 2. ALL NEW FIRE FIRE ALARM EQUIPMENT | | | THAT MONITORS FIRE SPRINKLER SYSTEMS | | | SHALL BE MONITORED BY A UL LISTED | | | CENTRAL STATION APPROVED FOR CENTRAL | | | STATION SERVICE. | | | | | | 3. A SMOKE DETECTOR WILL BE REQUIRED | | | ABOVE THE PANEL IF PANEL LOCATION | | | IS APPROVED. | | | | | | 4. BUILDING ADDRESS REQUIRED. A MINIMUM | | | OF 6" HIGH NUMBERS ARE REQUIRED. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|