| Plan Review Notes For Permit 05010848 |
| Permit Number |
05010848 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-01-24 00:00:00 | ************* UNSAT ***************** | | | | | | 1)NOTE: PLEASE INCLUDE ALL LICENSE #'S | | | IN TITLE BLOCK AS REQUIRED UNDER FAC | | | 61G15-23.002 AND PER FS 471.023 | | | THIS IS REQUIRED FOR ALL TRADE SHEETS | | | WHEATHER OR NOT COMMENT IS MADE BY OTHER | | | REVIEWER(S). | | | | | | 2)NOTE: PLEASE SEE SEC'S ARE SHOWN AS | | | 1/0'S, HOWEVER SERVICE IS SHOWN AS 200A | | | METER/MAIN. . PLEASE SEE 310.16 FOR MIN | | | SIZE OF SEC'S. | | | | | | 3)NOTE: PLEASE SHOW LOAD CALCULATION AND | | | SHOW CONTINUOUS LOADS AT 125%. | | | 220.3, 220.10.220.13 215.3,230.42 ETC. | | | 215.5 | | | | | | 4)NOTE: PLEASE SEE MISSING CWP AS PART | | | OF THE GROUNDING ELECTRODE SYSTEM PER | | | 250.50 | | | | | | 5)NOTE: PLEASE SEE HAND DRAWN CHAGES ON | | | PLANS ARE NOT PERMITTED TO SIGNED AND | | | SEALED PLANS. | | | FS 471.025 ETC. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | | | | PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER REVIEWER(S) WHICH MAY AFFECT | | | ELECTRICAL PLANS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|