| Date |
Text |
| 2005-01-27 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05010848 |
| | ADD: 503 M ST |
| | CONT: GRAYHAWL DEVELOPMENT |
| | TEL: (561)662-8150 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | |
| | 1)PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) INCLUDE ALL LICENSE NUMBER'S INTHE |
| | TITLE BLOCKAS REQUIRED UNDER FAC |
| | 61G15-23.002 AND FL S S 471.023. |
| | |
| | 3) HAND DRAWN CHANGES TO SEALED PLANS |
| | ARE NOT PERMITTED SEE 471.025 |
| | |
| | 4) RESTROOMS INDICATE A 4" RISE FROM THE |
| | ADJACENT GRADE SEE:11-4.1.3(1) AT |
| | LEAST ONE ACCESSIBLE ROUTTE COMPLYING |
| | WITH 11-4.3 SHALL CONNECT ACCESSIBLE |
| | BUILDING OR FACILITY ENETRANCES WITH ALL |
| | ACCESSIBLE SPACES AND ELEMENTS WITHIN |
| | THE BUILDING OR FACILITY. |
| | 11-4.1.2 VERTICAL ACCESSIBILITY, |
| | NOTHING IN THIS CODE SHALL BE CONSTRUED |
| | TO RELIEVE THE OWNER OF ANY BUILDING, |
| | SSTRUCTURE OR FACILITY FROM THE DUTY TO |
| | PROVIDE VERTICAL ACCESSIBILITY TO ALL |
| | LEVELS ABOVE OR BELOW THE OCCUPIAABLE |
| | GRADE LEVEL. |
| | |
| | 5) FL BLD CODE 1804.2.2 QUESTIONABLE |
| | SOILS, WHERE THE BEARING CAPACITY IS |
| | NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| | WHERE THE BEARING CAPACITY OF THE SOIL |
| | IS NOT DEFINITLY KNOWN OR IS IN QUESTION |
| | THE BUILDING OFFICIAL MAY REQUIRE EXPLOR |
| | ATIONS, TEST OR OTHER ADEQUATE PROOF AS |
| | TO THE PERMISSIBLE SAFE BEARING |
| | CAPACITY. REQUIRED TEST AND RECOMMENDA- |
| | TIONS SUBMITTED TO VERIFY BEARING CAPA- |
| | CITY SHALL BE CERTIFIED BY A GEOTECH- |
| | NICALREPORT FROM A DESIGN PROFESSIONAL |
| | PROPERLY LICENSED IN THE STATE OF |
| | FLORIDA. |
| | |
| | 6)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 7)FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) SOLID EXTERIOR DOORS |
| | B) LOUVERS |
| | C) TRUSS ANCHORS |
| | D) ROOFING ASSEMBLIES |
| | |
| | 8) SHEET A-3 FOUNDATION REQUIRES: |
| | 1804.1.3 THE BOTTOM OF THE FOUNDATION |
| | SHALL EXTEND NO LESS THAN 12" |
| | BELOW FINISH GRADE. |
| | |
| | 9) A-2 TIE BEAM NOTE 2121.2.3.2 NOTE IS |
| | NOT APPLICABLEIT IS FOR HIGH VELOCITY |
| | HURRICANE WIND ZONE DADE & BROWARD |
| | COUNTIES. |
| | |
| | 10) A-3 NOTE DEALS WITH 2319.17.1.2 ALSO |
| | DEALS WITH THE HIGH VELOCITY WIND ZONE, |
| | DADE & BROWARD COUNTIES, NOT |
| | APPLICABLE. |
| | |
| | BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |