| Plan Review Notes For Permit 05010811 |
| Permit Number |
05010811 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-01-27 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SHT 1.1 SANITARY RISER DIAGRAM DOES | | | NOT MEET CODE REQUIREMENTS NOR DOES IT | | | REFLECT THE FLOOR PLAN. | | | A) RISER SHALL SHOW FIXTURES THAT ARE | | | INSTALLED AND NOT OPTIONAL FIXTURES. | | | SECTION 104.2.1. | | | B) POWDER ROOM SHOWS THE LAV ON THE | | | RIGHT SIDE OF THE ROOM AND THE W/C ON | | | THE LEFT SIDE ON THE RISER, BUT BOTH | | | FIXTURES ARE ON THE LEFT SIDE OF THE | | | ROOM ON THE FLOOR PLAN. PLEASE CORRELATE | | | THE RISER AND FLOOR PLAN. SECTION | | | 104.2.1. | | | C) LAUNDRY TRAY SHALL NOT DRAIN THROUGH | | | THE HORIZONTAL WET VENT FOR THE BATHROOM | | | FIXTURES. SECTION 909.1 | | | D) A CLEANOUT IS REQUIRED 4' ABOVE THE | | | FLOOR AT THE WASH MACHINE. SECTION | | | 708.10. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|