Plan Review Notes
Plan Review Notes For Permit 05010811
Permit Number 05010811
Review Stop P
Sequence Number 1
Notes
Date Text
2005-01-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT 1.1 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS NOR DOES IT
 REFLECT THE FLOOR PLAN.
 A) RISER SHALL SHOW FIXTURES THAT ARE
 INSTALLED AND NOT OPTIONAL FIXTURES.
 SECTION 104.2.1.
 B) POWDER ROOM SHOWS THE LAV ON THE
 RIGHT SIDE OF THE ROOM AND THE W/C ON
 THE LEFT SIDE ON THE RISER, BUT BOTH
 FIXTURES ARE ON THE LEFT SIDE OF THE
 ROOM ON THE FLOOR PLAN. PLEASE CORRELATE
 THE RISER AND FLOOR PLAN. SECTION
 104.2.1.
 C) LAUNDRY TRAY SHALL NOT DRAIN THROUGH
 THE HORIZONTAL WET VENT FOR THE BATHROOM
 FIXTURES. SECTION 909.1
 D) A CLEANOUT IS REQUIRED 4' ABOVE THE
 FLOOR AT THE WASH MACHINE. SECTION
 708.10.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]