| Plan Review Notes For Permit 05010754 |
| Permit Number |
05010754 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-01-28 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE PROVIDE A CALCULATION INCLUDI- | | | NG ALL ADDED LOADS IMPOSED,ALL EXISTING | | | LOADS. THE A/C,WATER HEATER AND POOL | | | EQUIPMENT IN POOL HOUSE ARE NOT SHOWN ON | | | THE CALC'S. | | | | | | 2} THERE IS NO LAUNDRY CIRCUIT IN THE | | | CALCULATION PER 220.16(B). | | | | | | 3} THERE IS NO DRYER IN THE CALCULATION | | | PER 220.18. | | | | | | 4} THE TWO RISER DIAGRAMS DO NOT | | | CORRELATE. IS THE 150 AMP PANEL FED FROM | | | THE METER OR THE200 AMP HOUSE PANEL? | | | | | | 5} SHOW LOCATION OF ALL SERVICE | | | EQUIPMENT ON THE POOL HOUSE ON THE | | | PLAN. | | | | | | 6} SHOW 150 AMP PANEL SCHEDULE AND | | | GROUNDING PER 250.32 | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|