| Plan Review Notes For Permit 05010754 |
| Permit Number |
05010754 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-02-07 00:00:00 | DENIED | | | | | | 1.PLEASE SIGN OWNER/AGENT ON ENERGY | | | CALCS. | | | | | | 2.1015.2 HEIGHT. GUARDRAILS SHALL | | | FORM A VERTICAL PROTECTIVE BARRIER NOT | | | LESS THAN 42" HIGH. | | | 1015.3 OPENINGS. OPEN GUARDRAILS | | | SHALL HAVE INTERMEDIATE RAILS OR ORNA- | | | MENTAL PATTERNS SUCH AS A 4" DIAMETER | | | SPHERE CAN NOT PASS THROUGH. A BOTTOM | | | RAIL OR CURB SHALL BE PROVIDED THAT WILL | | | REJECT THE PASSAGE OF 2" DIAMETER | | | SPHERE. | | | | | | 3.ROOFING DETAILS ON PLANS SPEC A | | | METAL ROOF. PRODUCT APPROVALS ARE FOR | | | COMP. SHINGLES.PLEASE VERIFY. | | | | | | 4.SHOW SIZE AND LOCATION OF ATTIC | | | ACCESS COMPLYING WITH FBC 2309.6 | | | | | | ANY QUESTIONS CALL ME. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|