| 2005-06-03 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | F.S.= FLORIDA (STATE) STATUTE |
| | |
| | FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| | ARE NUMBERED AS PER THE BUILDING PLAN |
| | REVIEW OF 02/09/05: |
| | |
| | 1) 713.13 F.S.A NOTICE OF COMMENCEMENT |
| | SHALL BE RECORDED AT PALM BEACH COUNTY |
| | COURTHOUSE AND A COPY SUBMITTED TO THIS |
| | OFFICE BEFORE A PERMIT CAN BE ISSUED. |
| | BLANK FORMS ARE AVAILABLE FROM THIS |
| | OFFICE. |
| | NOTE: THE NOTICE OF COMMENCEMENT MUST BE |
| | RE-RECORDED IF THE DESCRIBED IMPROVEMENT |
| | OR CONSTRUCTION IS NOT COMMENCED WITHIN |
| | 90 DAYS OF RECORDING. |
| | |
| | 3) FBC* F102.2.7THIS COMMENT HAS NOT |
| | BEEN PROPERLY ADDRESSED.ARCHITECTURAL |
| | TRIM, ON BUILDINGS LOCATED IN THE FIRE |
| | DISTRICT, SHALL BE CONSTRUCTED OF |
| | APPROVED NON-COMBUSTIBLE MATERIALS OR |
| | FIRE RETARDANT TREATED WOOD.THE |
| | COMMENT RESPONSE IS NOTED BUT SHEET |
| | A-2.04 KEY NOTE 5, SHEET A-2.05 KEY |
| | NOTES 2 AND 7 AND SECTION A-7.01/1 ALL |
| | STILL MAKE REFERENCE TO FOAM MOLDINGS |
| | AND/OR EIFS SYSTEM.SHEET A-8.01 |
| | 'MATERIALS NOTES' 13 AND 21, REFERENCED |
| | ON DETAILS 1, 4, 7 AND 11, REFER TO |
| | CONTINUOUS PLYWOOD SHEATHING.ALSO, |
| | SHEET A-10.01 'MATERIALS NOTE' 19, |
| | REFERENCED ON DETAILS 1 TO 7, 11 AND 12 |
| | REFER TO EIFS.THESE ARE ALL |
| | COMBUSTIBLE MATERIALS NOT PERMITTED IN |
| | THE FIRE DISTRICT.AMENDTHE PLANS TO |
| | DEMONSTRATE COMPLIANCE. |
| | |
| | 5) PROVISO: |
| | FBC 1601.1SHEET A-8.01 STILL DOES NOT |
| | DESCRIBE THE FASTENERS FOR ATTACHMENT OF |
| | THE PROPOSED DECORATIVE MOLDINGS. |
| | SUBMIT SUB-CONTRACTOR'S SHOP DRAWINGS |
| | FOR REVIEW BEFORE |
| | INSTALLATION/INSPECTION. |
| | |
| | 7) STOREFRONT WINDOWS |
| | (A) FBC 1606.1WINDOW LOADS.SHEET |
| | A-2.01 KEY NOTE 16 STATES THAT NEW |
| | WINDOWS ARE TO BE INSTALLED IN FRONT OF |
| | THE EXISTING WINDOWS SO NO PRODUCT |
| | APPROVAL IS REQUIRED.IF NO PRODUCT |
| | APPROVALS ARE TO BE PROVIDED, THEN AMEND |
| | THE PLANS TO INCLUDE DETAILS SHOWING |
| | ADEQUATE ATTACHMENT OF THE OF THE |
| | WINDOWS TO THE BUILDING. |
| | (B) FBC 2405.2.1(4) SAFETY GLASS.IT |
| | IS NOTED THAT THE WINDOW SCHEDULE ON |
| | SHEET A-10.01 STATES THAT THE NEW |
| | WINDOWS WILL BE IMPACT RATED BUT UNLESS |
| | A PRODUCT APPROVAL IS SUBMITTED TO |
| | VERIFY THIS, THE PLANS MUST BE ANNOTATED |
| | TO DEMONSTRATE COMPLIANCE WITH THE |
| | REQUIREMENTS OF THE CONSUMER PRODUCT |
| | SAFETY COMMISSION 16, CODE OF FEDERAL |
| | REGULATIONS, PART 1201 (CPSC 16-CFR, |
| | PART 1201). |
| | |
| | 9) ONE COPY OF THE OLD/VOID SHEETS WERE |
| | NOT INCLUDED WITH THE RESUB AS REQUESTED |
| | TO EXPEDITE REVIEW OF A RESUBMITTAL |
| | WHICH REQUIRES NEW PLANS IN ORDER TO |
| | ADDRESS THE ABOVE COMMENTS, THE OLD |
| | SHEETS SHALL BE REMOVED AND THE NEW |
| | SHEETS INSERTED.ONE COPY OF EACH OLD |
| | SHEET SHOULD BE STAPLED/CLIPPED TO THE |
| | REMAINING OLD SHEETS, TO FORM A SET OF |
| | 'OLD/VOID SHEETS', FOR COMPARISON OF |
| | REVISIONS WHEN REVIEWING THE RESUBMITTED |
| | PLANS. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | TELEPHONE: (561) 805 6716ROBERT BROWN |
| | E-MAIL: [email protected] |