2005-06-03 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 02/09/05:
  
 1) 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 3) FBC* F102.2.7THIS COMMENT HAS NOT
 BEEN PROPERLY ADDRESSED.ARCHITECTURAL
 TRIM, ON BUILDINGS LOCATED IN THE FIRE
 DISTRICT, SHALL BE CONSTRUCTED OF
 APPROVED NON-COMBUSTIBLE MATERIALS OR
 FIRE RETARDANT TREATED WOOD.THE
 COMMENT RESPONSE IS NOTED BUT SHEET
 A-2.04 KEY NOTE 5, SHEET A-2.05 KEY
 NOTES 2 AND 7 AND SECTION A-7.01/1 ALL
 STILL MAKE REFERENCE TO FOAM MOLDINGS
 AND/OR EIFS SYSTEM.SHEET A-8.01
 'MATERIALS NOTES' 13 AND 21, REFERENCED
 ON DETAILS 1, 4, 7 AND 11, REFER TO
 CONTINUOUS PLYWOOD SHEATHING.ALSO,
 SHEET A-10.01 'MATERIALS NOTE' 19,
 REFERENCED ON DETAILS 1 TO 7, 11 AND 12
 REFER TO EIFS.THESE ARE ALL
 COMBUSTIBLE MATERIALS NOT PERMITTED IN
 THE FIRE DISTRICT.AMENDTHE PLANS TO
 DEMONSTRATE COMPLIANCE.
  
 5) PROVISO:
 FBC 1601.1SHEET A-8.01 STILL DOES NOT
 DESCRIBE THE FASTENERS FOR ATTACHMENT OF
 THE PROPOSED DECORATIVE MOLDINGS.
 SUBMIT SUB-CONTRACTOR'S SHOP DRAWINGS
 FOR REVIEW BEFORE
 INSTALLATION/INSPECTION.
  
 7) STOREFRONT WINDOWS
 (A) FBC 1606.1WINDOW LOADS.SHEET
 A-2.01 KEY NOTE 16 STATES THAT NEW
 WINDOWS ARE TO BE INSTALLED IN FRONT OF
 THE EXISTING WINDOWS SO NO PRODUCT
 APPROVAL IS REQUIRED.IF NO PRODUCT
 APPROVALS ARE TO BE PROVIDED, THEN AMEND
 THE PLANS TO INCLUDE DETAILS SHOWING
 ADEQUATE ATTACHMENT OF THE OF THE
 WINDOWS TO THE BUILDING.
 (B) FBC 2405.2.1(4) SAFETY GLASS.IT
 IS NOTED THAT THE WINDOW SCHEDULE ON
 SHEET A-10.01 STATES THAT THE NEW
 WINDOWS WILL BE IMPACT RATED BUT UNLESS
 A PRODUCT APPROVAL IS SUBMITTED TO
 VERIFY THIS, THE PLANS MUST BE ANNOTATED
 TO DEMONSTRATE COMPLIANCE WITH THE
 REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201).
  
 9) ONE COPY OF THE OLD/VOID SHEETS WERE
 NOT INCLUDED WITH THE RESUB AS REQUESTED
 TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN