Plan Review Notes
Plan Review Notes For Permit 05010680
Permit Number 05010680
Review Stop B
Sequence Number 1
Notes
Date Text
2005-02-09 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) 713.13 F.S.A NOTICE OF
 COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST
 BE
 RE-RECORDED IF THE DESCRIBED
 IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2) SHEET FBC* 104.2.1SHEET S2.0, THE
 FOUNDATION PLAN STATES "F2 NEW FTG", AT
 GRID 2A, UNDER EXISTING W10X49 COLUMNS.
 HOW IS A NEW FOOTING TO BE CAST UNDER
 EXISTING COLUMNS.CROSS-SECTION 2/S3.0
 DOES NOT SHOW HOW THIS IS TO BE
 ACHIEVED.ANNOTATE THE PLANS TO
 CLARIFY
 THE DESIGN INTENTION.
  
 3) FBC* F102.2.7ARCHITECTURAL TRIM,
 ON
 BUILDINGS LOCATED IN THE FIRE DISTRICT,
 SHALL BE CONSTRUCTED OF APPROVED
 NON-COMBUSTIBLE MATERIALS OR FIRE
 RETARDANT TREATED WOOD.SHEET A-2.04
 KEY NOTE 5, SHEET A-2.05 KEY NOTES 2
 AND
 7, SHEET A-5.01 KEY NOTES 2 AND 7,
 SHEET
 A-7.01 AND SHEET A-8.01 ALL MAKE
 REFERENCE TO FOAM MOLDINGS AND/OR EIFS
 SYSTEM.THESE ARE COMBUSTIBLE
 MATERIALS
 NOT PERMITTED IN THE FIRE DISTRICT.
 AMEND THE PLANS TO DEMONSTRATE
 COMPLIANCE.
  
 4)) FBC* F102.2.4ROOF COVERINGS, ON
 BUILDINGS LOCATED IN THE FIRE DISTRICT,
 SHALL CONFORM TO THE REQUIREMENTS OF
 CLASS A OR B ROOF COVERINGS, AS DEFINED
 IN FBC 1505.ANNOTATE THE PLANS TO
 DEMONSTRATE COMPLIANCE.
  
 5) FBC 1601.1SHEET A-8.01.SUBMIT
 DETAILS TO SHOW THE METHOD OF ATTACHMENT
 FOR THE PROPOSED DECORATIVE MOLDINGS
  
 6) SHEET S3.0, CROSS-SECTIONS 1 AND 2
 HAVE NOTES STATING THAT THE METAL STUDS
 ARE ATTACCHED TO THE STRUCTURAL STEEL
 USING 0.145" DIA PDF.SHOULD THIS BE
 PAF (POWDER ACTUATED FASTENERS) AS
 LISTED ON SHEET S2.0 STRUCTURAL
 ABBREVIATIONS?IF NOT, ANNOTATE THE
 PLANS TO CLARIFY THE TYPE OF FASTENER TO
 BE USED.
  
 7) SUBMIT PRODUCT APPROVALS FOR:
 - NEW ROOFING SYSTEM
 - NEW ALUMINUM STOREFRONT
 - NEW STOREFRONT DOORS (INCLUDING
  
 AUTOMATIC OPENING DOORS, IF
 DIFFERENT).
 NOTE: FL. ADMIN CODE RULE 9B-72 (IN
 EFFECT SINCE OCTOBER 1, 2003) REQUIRES
 THAT PRODUCTS HAVE STATEWIDE, LOCAL OR
 SITE-SPECIFIC PRODUCT APPROVAL.THE
 SUBMITTAL SHOULD INCLUDE THE STATEWIDE
 PRODUCT APPROVAL NUMBER (FL###),
 AVAILABLE FROM THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE
 WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP
 (IF YOU FIND THAT THE QUOTED WEB PAGE
 IS
 NO LONGER AVAILABLE, PLEASE INFORM THE
 PLAN REVIEWER)
 THE PRODUCT APPROVAL SHEETS SHALL BE
 MARKED, AS APPROPRIATE, TO IDENTIFY
 WHICH PRODUCT OPTIONS/MATERIALS/SIZES
 ARE TO BE USED.
  
 8) FBC 3502SHEET S2.0, CONCRETE AND
 REINFORCING NOTE C1 REFERS TO ACI
 318-99.FLORIDA BUILDING CODE CITES ACI
 318-02 AS THE REFERENCED VERSION OF THAT
 STANDARD.AMEND THE NOTE.
  
 9) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]