| 2005-02-03 00:00:00 | PAY BALANCEBUILDING PLAN REVIEW |
| | PERMIT: 05100646 |
| | ADD: 1597 HAWKS LANDING |
| | CONT: DREAMSTAR |
| | TEL: (561)694-7750 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | |
| | 1)PROVIDE NOC RECORDED WITH THE CLERK OF |
| | COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) PAY THE BALANCE DUE ON PERMIT OF |
| | $2,325.75. |
| | |
| | 3) SHEET A-3 TRUSS ANCHOR "D" VALUE IS |
| | HIGH, SEE 2005 USP CATALOG, 2 PLY IS |
| | 4255 & 3 PLY IS 6110. |
| | |
| | 4) SHEET A-3 ROOF FRAMING PLAN, MISSING |
| | GIRDERS AT THE BACK COVERED PORCH |
| | TRUSSES ARE CANTILEVERED 14'-10". |
| | |
| | 5A) FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | THERE IS NO FRAMING DETAILS FOR THE |
| | CHIMNEY? |
| | 5B) WITH A PREMANUFACTURED CHIMNEY |
| | APPROVAL FROM THE MANUFACTURER WILL BE |
| | REQUIRED FOR THE CHIMNEY CAP ENCLOSURE, |
| | SINCE IT MAY NOT BE ABLE TO PULL A |
| | DRAFT. |
| | |
| | 6) 2804.4.1 FACTORY-BUILT CHIMNEYS |
| | FACTORY BUILT CHIMNEYS SHALL BE LISTED |
| | AND SHALL BE INSTALLED IN ACCORDANCE |
| | WITH THE CONDITIONS OF THE LISTING, AND |
| | MANUFACTURER'S INSTRUCTION. |
| | |
| | 7) CHIMNEYS FOR THE USE WITH FACTORY- |
| | BUILT FIREPLACES SHALL MEET THE |
| | REQUIREMENTS OF UL 127. |
| | |
| | 8) 2806.1.2 FACTORY BUILT FIREPLACES |
| | SHALL BE TESTED IN ACCORDANCE WITH AND |
| | MEET THE REQUIREMENTS OF UL 127. |
| | |
| | 9) 2804.4.4. FACTORY-BUILT CHIMNEYS FOR |
| | USE WITH CLOSED COMBUSTION WOOD BURNING |
| | APPLIANCES SHALL COMPLY WITH |
| | THE TYPE HT REQUIREMENT UL 103. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |