Plan Review Notes
Plan Review Notes For Permit 05010631
Permit Number 05010631
Review Stop M
Sequence Number 1
Notes
Date Text
2005-01-26 00:00:00DENIED:
 1.PLAN SHEET M-1 INDICATES RETURN AIR
 GRILLES FROM THE FILING ROOM AND ALSO BY
 THE MENS ROOM.PLAN DOES NOT INDICATE A
 DUCTED RETURN BACK TO THE AHU.WILL
 THESE AREAS BE A RETURN AIR PLENUM?
 PLEASE NOTE AIR FROM THE RESTROOM IS NOT
 TO BE RECIRCULATED.
  
 2.NO COMBUSTIBLES ALLOWED ABOVE THE
 CEILING IN THE RETURN AIR PLENUM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  