| Plan Review Notes For Permit 05010600 |
| Permit Number |
05010600 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-01-24 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE PROVIDE LOAD CALCULATIONS, | | | RISER DIAGRAM AND PANEL(S) SCHEDULE. | | | INDICATE IF SERVICE IS NEW OR EXISTING. | | | 215.5 | | | | | | 2} PROVIDE A FLOOR PLAN THAT INDICATES | | | LOCATION OF KITCHEN COUNTERTOPS AND | | | APPLIANCES SO THAT COMPLIANCE WITH | | | 210.52 CAN BE DETERMINED. ALSO SEE THE | | | ELECTRICAL FLOOR PLANS DIFFER FROM | | | ARCHITECTURALS. PLEASE CORRELATE. | | | | | | 3} PLEASE INDICATE LOCATIONS OF A/C | | | EQUIPMENT ON PLAN, VERIFY COMPLIANCE | | | WITH 210.63 & 210.70(A)(3). | | | | | | 4} LOCATE FRONT AND REAR RECEPTACLES PER | | | 210.52(E). | | | | | | 5} INDICATE THE FUNCTION OF THE DEVICES | | | THAT APPEAR TO BE LOCATED IN A CLOSET IN | | | THE KITCHEN. | | | | | | 6} PER 104.2.1 FBC THE DESIGNER OF | | | RECORD MUST PRINT NAMEAND SIGN THE | | | PLAN(S) THEY ARE RESPONSIBLE FOR. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|