| 2005-03-09 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | F.S.= FLORIDA (STATE) STATUTE |
| | |
| | FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| | ARE NUMBERED AS PER THE BUILDING PLAN |
| | REVIEW OF 1/18/05: |
| | |
| | 4) IMPACT FEES. THE PLANS SHALL BE TAKEN |
| | TO PALM BEACH COUNTY BUILDING DEPARTMENT |
| | FOR IMPACT FEE ASSESSMENT. THEY SHALL BE |
| | STAMPED AT THAT OFFICE AND A COPY OF THE |
| | PAID RECEIPT SUBMITTED TO THE CITY OF |
| | WEST PALM BEACH DEPT OF CONSTRUCTION |
| | SERVICES BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 5) FBC* 105.13.1SUBMITTAL OF SIGNED |
| | COPIES OF THE STRUCTURAL INSPECTION PLAN |
| | IS NOTED. UNDER SECTION C, THE LIST OF |
| | STRUCTURAL PLANS SHOULD INCLUDE SHEETS |
| | S-5.5, S-5.6 AND S-5.7.ADD THESE TO |
| | THE INSPECTION PLAN.ALSO, UNDER |
| | SECTION B, THE INSPECTION PLAN MAKES |
| | REFERENCE TO ACI 318-99.THE VERSION OF |
| | THIS STANDARD REFERENCED BY FLORIDA |
| | BUILDING CODE IS ACI 318-02. THIS |
| | COMMENT WAS MADE PREVIOUSLY IN THE PLAN |
| | REVIEW FOR THE BUILDING PERMIT |
| | APPLICATION #04120353 PERTAINING TO PLAN |
| | SHEET S-0.0 (SEE COMMENT #12 BELOW). |
| | AMEND THE INSPECTION PLAN. |
| | |
| | 8) FBC 1606.1.1SHEET S-0.0, GENERAL |
| | NOTES, WIND LOADS.THIS COMMENT HAS NOT |
| | BEEN ADDRESSED.SUBMIT THREE COPIES |
| | OF THE RWDI WIND TUNNEL TEST REPORT# |
| | 04-1598 AS REFERENCED UNDER THE 'WIND |
| | LOADS' NOTE. |
| | |
| | 9) FBC* 104.2.1IT IS NOTED THAT SHEETS |
| | S-0.3 AND S-5.1, WHICH INCLUDE |
| | FOUNDATION DETAILS, HAVE STILL NOT BEEN |
| | INCLUDED IN THE FOUNDATION PERMIT |
| | APPLICATION PLAN SETS.NOTE THAT EACH |
| | PLAN SET SHALL INCLUDE ALL SHEETS THAT |
| | SHOW FOUNDATION DETAILS. |
| | |
| | 12) FBC 3502SHEET S-0.0, GENERAL |
| | NOTES THE PLANS REFERENCE ACI 530.1-99 |
| | AND ACI 318-99 (TWICE) UNDER THE |
| | SUB-TITLES 'CODES' AND 'THRESHOLD |
| | BUILDING INSPECTION PLAN'.THE VERSIONS |
| | OF THESE STANDARDS REFERENCED BY FLORIDA |
| | BUILDING CODE ARE ACI 530.1-02 AND ACI |
| | 318-02. AMEND THE GENERAL NOTES. |
| | |
| | 13) FBC 3502SHEET S-0.0, GENERAL NOTES |
| | THE PLANS REFERENCE ASTM A 185-85 AND |
| | ASTM A 615-84A (TWICE) UNDER THE |
| | SUB-TITLES 'WELDED WIRE FABRIC' AND |
| | 'REINFORCING STEEL'.THE VERSIONS OF |
| | THESE STANDARDS REFERENCED BY FLORIDA |
| | BUILDING CODE ARE ASTM A 185-97 AND |
| | ASTM A 615-94.AMEND THE GENERAL NOTES. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | TELEPHONE: (561) 805 6716ROBERT BROWN |
| | E-MAIL: [email protected] |