Plan Review Notes
Plan Review Notes For Permit 05010583
Permit Number 05010583
Review Stop M
Sequence Number 1
Notes
Date Text
2005-01-19 00:00:00DENIED:
 PLAN SHEET M-2 HEAT PUMP DETAIL; SNOTE
 INDICATES "DUCT SMOKE DETECTOR UNITS
 2000 CFM AND OVER".PER 2001 FBC(M)
 606.2.2, WHERE MULTIPLE AHU SYSTEMS
 SHARE A COMMON PLENUM WITH A DESIGN
 CAPACITY GREATER THAN 2,000 CFM, THE
 RETURN & SUPPLY AIR SHALL BE PROVIDED
 WITH DUCT SMOKE DETECTORS.PLEASE
 REVISE PLANS ACCORDINGLY.
  