| Plan Review Notes For Permit 05010583 |
| Permit Number |
05010583 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-01-19 00:00:00 | DENIED: | | | PLAN SHEET M-2 HEAT PUMP DETAIL; SNOTE | | | INDICATES "DUCT SMOKE DETECTOR UNITS | | | 2000 CFM AND OVER".PER 2001 FBC(M) | | | 606.2.2, WHERE MULTIPLE AHU SYSTEMS | | | SHARE A COMMON PLENUM WITH A DESIGN | | | CAPACITY GREATER THAN 2,000 CFM, THE | | | RETURN & SUPPLY AIR SHALL BE PROVIDED | | | WITH DUCT SMOKE DETECTORS.PLEASE | | | REVISE PLANS ACCORDINGLY. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | |
|