| Date |
Text |
| 2005-03-25 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)SEE PREVIOUS LIST, INDICATE METHOD |
| | OF INSTALLATION AND WHICH PRODUCT IS |
| | BEING INSTALLED.A RESPONSE WAS |
| | PROVIDED - "WITH A DRILL".THIS DOES |
| | NOT SHOW CODE COMPLIANCE.THERE ARE TWO |
| | ACCORDIAN SHUTTERS WITH VARIOUS METHODS |
| | OF ATTACHMENT ON YOUR PRODUCT APPROVAL. |
| | PLEASE CIRCLE WHICH PRODUCT YOU ARE |
| | USING AND CIRCLE THE DRAWING WHICH SHOWS |
| | METHOD OF INSTALLATION (INSIDE MOUNT, |
| | WALL MOUNT, ETC).SHEET 6 HAS THE |
| | TAPCON FASTENERS FOR THE 6.8 ACCORDIAN |
| | SHUTTER HIGHLIGHTED, BUT BOTH THE 2" |
| | EDGE DISTANCE AND 3" EDGE DISTANCE ARE |
| | HIGHLIGHTED.IS THIS CORRECT? |
| | |
| | 2.)IN RESPONSE TO THE PREVIOUS REQUEST |
| | TO FILL OUT THE SCHEDULE FOR |
| | INSTALLATION, A WALL PRESSURE WAS |
| | PROVIDED OF -30/-175.OPENINGS HAVE A |
| | POSITIVE AND NEGATIVE PRESSURE; HOW HAVE |
| | YOU ARRIVED AT TWO NEGATIVE NUMBERS? |
| | PLEASE PROVIDE CORRECT DP.IF THIS IS A |
| | ONE STORY SINGLE FAMILY DWELLING, THE |
| | -30 IS TOO LOW AND THE -175 IS TOO HIGH. |
| | SEE FBC TABLE1606.2B AND D, AND FIGURE |
| | 1606.2(C). |
| | |
| | 3.)SEE PREVIOUS LIST, ITEM #3, FLORIDA |
| | STATE PRODUCT APPROVAL OR LOCAL PRODUCT |
| | APPROVAL REQUIRED IN ADDITION TO TEST |
| | REPORT, WWW.FLORIDABUILDING.ORG. |
| | |
| | 4.)SHOW EMERGENCY MEANS OF ESCAPE |
| | FBC1005.4.4. |