 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
  
 1}PLEASE PROVIDE A CALCULATION
 INCLUDING ALL ADDED LOADS IMPOSED & ALL
 EXISTING LOADS.
  
 2}WET BAR SINKS ? WHERE THE
 RECEPTACLES ARE INSTALLED TO SERVE THE
 COUNTERTOP SURFACES AND ARE LOCATED
 WITHIN 1.8 M (6 FT) OF THE OUTSIDE EDGE
 OF THE WET BAR SINK. 201.8(A)(7).
  
 3} A RECEPTACLE MUST BE PROVIDED FOR THE
 A/C UNITS PER 210.63.
  
 4} THE DESIGNER OF RECORD MUST PRINT AND
 SIGN THE PLANS PER 104.2.1 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  