| Plan Review Notes For Permit 05010499 |
| Permit Number |
05010499 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-01-19 00:00:00 | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | | | | 1}PLEASE PROVIDE A CALCULATION | | | INCLUDING ALL ADDED LOADS IMPOSED & ALL | | | EXISTING LOADS. | | | | | | 2}WET BAR SINKS ? WHERE THE | | | RECEPTACLES ARE INSTALLED TO SERVE THE | | | COUNTERTOP SURFACES AND ARE LOCATED | | | WITHIN 1.8 M (6 FT) OF THE OUTSIDE EDGE | | | OF THE WET BAR SINK. 201.8(A)(7). | | | | | | 3} A RECEPTACLE MUST BE PROVIDED FOR THE | | | A/C UNITS PER 210.63. | | | | | | 4} THE DESIGNER OF RECORD MUST PRINT AND | | | SIGN THE PLANS PER 104.2.1 FBC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | AND | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|