| 2005-02-23 00:00:00 | ********* UNSAT 2ND REVIEW ********* |
| | |
| | 1)NOTE: PLEASE SEE COMMENTS FROM |
| | PREVIOUS REVIEW. |
| | PLEASE SEE RESPONSE LETTER MENTIONS WORK |
| | ONLY TO BE DONE IN KITCHEN AND NEW |
| | STAIR. |
| | PLEASE SUBMIT ELECTRICAL PLANS WHICH |
| | ONLY INDICATE WORK TO BE DONE. |
| | ELECTRICAL NOTES MENTIONS MORE WORK THAN |
| | WHAT IS MENTIONED IN RESPONSE LTR. |
| | PLEASE SEE ELECTRICAL PLAN SHOWS MANY |
| | OTHER ELECTRICAL ITEMS TO BE DONE?? |
| | IF HOUSE IS BEING REMODELED/ REWIRED, |
| | PLEASE SHOW ALL REQUIRED PER 2002 NEC |
| | AND NFPA-72. |
| | |
| | 2)NOTE: PLEASE SEE PLANS WHICH ARE |
| | SIGNED AND SEALED BY AN ARCH/ ENGINEER |
| | ARE NOT PERMITTED TO HAND-DRAWN CHANGES |
| | AND "WHITE-OUT" ON PLANS. PLEASE SEE |
| | HAND DRAWN CHANGES REQUIRED EACH CHANGE |
| | TO BE SIGNED, DATED. |
| | PLEASE SUBMIT NEW REPRINTED SIGNED, |
| | DATED AND SEALED PLANS. |
| | FS 481.221 |
| | |
| | 3)NOTE: PLEASE SEE 210.52C1 FOR KITCHEN |
| | COUNTERSPACE RECEPT SPACING. |
| | PLEASE ALSO SEE 210.8A6 FOR REQUIRED GFI |
| | PROTECTION. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | NOTE ADDED: |
| | |
| | PLEASE REMOVE ANY OLD/VOIDED SHEETS AND |
| | INSERT NEW REVISED SHEETS INTO TWO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |