| Plan Review Notes For Permit 05010477 |
| Permit Number |
05010477 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-01-11 00:00:00 | PROVISO: | | | REMOVAL OF AHU AND DUCTWORK CAN BE DONE | | | PLEASE PROVIDE THE FOLLOWING PRIOR TO | | | WORK COMMENCING: | | | 1.LAYOUT OF DUCTWORK; PROVIDE DUCT | | | SIZE, MATERIAL AND GRILLE/CAN SIZE. | | | 2.AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED. | | | 3.DUCT SMOKE DETECTOR SHALL HAVE | | | NOTIFICATION TO ALARM/STROBE IN | | | NORMMALLY OCCUPIED AREAS, PER 2001 | | | FBC(M)606.4.1 #2. | | | 4.INDICATE TERMINATION OF THE EXHAUST | | | TO THE "RE-LOCATED" HOOD.COMPLY WITH | | | 2001 FBC(M)506.3.14.3. | | | 5.PROVIDE OUTSIDE AIR CALCULATIONS PER | | | 2001 FBC(M) TABLE 403.3. | | | 6.INDICATE OUTSIDE AIR INTAKE, DUCT | | | SIZE AND MATERIAL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|