| Plan Review Notes For Permit 05010448 |
| Permit Number |
05010448 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-01-21 00:00:00 | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | THE FOLLOWING CORRECTIONS ARE FOR THE | | | DUPLEX SERVICE. | | | | | | 1} THE LOAD CALCULATIONS SUBMITTED | | | REQUIRE A MINIMUM OF A 225 AMP SERVICE. | | | | | | THIS WOULD ALSO REQUIRE THE SERVICE | | | CONDUCTORS TO BE A MINIMUM OF 3/0 CU PER | | | 310.15(B)(6). | | | | | | 2} THE #3 CU FEEDER FROM THE DISCONNECT | | | TO THE PANEL IS REQUIRED TO BE #2 CU | | | MINIMUM PER 310.15(B)(6). | | | | | | 3} SHOW AII CONDUIT AND CONDUCTOR SIZES | | | ON RISER PER 215.5. | | | | | | THE FOLLOWING COMMENTS REFER TO THE | | | "COTTAGE" REWIRE. | | | | | | 1} THE PANEL LOCATION APPEARS TO BE IN | | | VIOLATION OF CLEARANCE REQUIREMENTS OF | | | 110.26. PLEASE INDICATE REMEDY FOR | | | COMPLIANCE. | | | | | | 2) PLEASE SEE RECEPTACLES NEED TO BE | | | ADDED IN THE FOLLOWING AREAS: | | | A) BEDROOMS 1,2& 3,LIVING ROOM, DINING | | | ROOM, AND "PORCH" FOR COMPLIANCE OF | | | 210.52(A), AND IN THE FRONT AND REAR OF | | | THE HOUSE FOR 210.52(E). | | | | | | ALSO PLEASE ADJUST THE VALUE ON THE | | | PERMIT TO REFLECT ALL LABOR AND MATERIAL | | | COSTS PER 104.6.5 FBC AMMENDMENTS,CWPB. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|