 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 THE FOLLOWING CORRECTIONS ARE FOR THE
 DUPLEX SERVICE.
  
 1} THE LOAD CALCULATIONS SUBMITTED
 REQUIRE A MINIMUM OF A 225 AMP SERVICE.
  
 THIS WOULD ALSO REQUIRE THE SERVICE
 CONDUCTORS TO BE A MINIMUM OF 3/0 CU PER
 310.15(B)(6).
  
 2} THE #3 CU FEEDER FROM THE DISCONNECT
 TO THE PANEL IS REQUIRED TO BE #2 CU
 MINIMUM PER 310.15(B)(6).
  
 3} SHOW AII CONDUIT AND CONDUCTOR SIZES
 ON RISER PER 215.5.
  
 THE FOLLOWING COMMENTS REFER TO THE
 "COTTAGE" REWIRE.
  
 1} THE PANEL LOCATION APPEARS TO BE IN
 VIOLATION OF CLEARANCE REQUIREMENTS OF
 110.26. PLEASE INDICATE REMEDY FOR
 COMPLIANCE.
  
 2) PLEASE SEE RECEPTACLES NEED TO BE
 ADDED IN THE FOLLOWING AREAS:
 A) BEDROOMS 1,2& 3,LIVING ROOM, DINING
 ROOM, AND "PORCH" FOR COMPLIANCE OF
 210.52(A), AND IN THE FRONT AND REAR OF
 THE HOUSE FOR 210.52(E).
  
 ALSO PLEASE ADJUST THE VALUE ON THE
 PERMIT TO REFLECT ALL LABOR AND MATERIAL
 COSTS PER 104.6.5 FBC AMMENDMENTS,CWPB.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW