| 2005-07-22 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUBMING |
| | FBC-2001 BUILDING |
| | |
| | A. THE PLANS HAVE BEEN CHANGED AND DO |
| | NOT SHOW ANY FACILITIES REQUIRED BY |
| | TABLE 403.1. NO RESPONSE TO FIRST REVIEW |
| | COMMENTS. |
| | 1. FELLOWSHIP HALL INDICATES 1,381SF |
| | BEING ADDED TO EXISTING CHURCH AREA. |
| | THIS WILL BE AN ASSEMBLY OCCUPANCY AND |
| | AS SUCH WILL ADD 198 MORE OCCUPANTS TO |
| | THE OCCUPANCY LOAD OF THE EXISTING |
| | STRUCTURES. TABLE 1003.1 |
| | 2. PER TABLE 403.1, 1 W/C FOR MEN AND 2 |
| | W/C'S FOR WOMEN, 1 LAV FOR MEN, 2 LAVS |
| | FOR WOMEN, A DRINKING FOUNTAIN AND A |
| | SERVICE SINK ARE REQUIRED. |
| | 3. SUBMIT A SANITARY AND A WATER RISER |
| | DIAGRAM IN ISOMETRIC FORM FOR REVIEW. |
| | SECTION 104.3.1.1. SHOW ALL PIPE SIZES, |
| | VENTS ECT FOR SANT., AND ALL PIPE SIZES, |
| | VALVES, RPZ BACKFLOW, WATER HAMMER |
| | ARRESTORS, (WHERE REQUIRED BY SECTION |
| | 604.9 LOCATED NEAR THE FIXTURE PER |
| | PDI-WH 201) AND POINT OF CONNECTION TO |
| | THE WATER SUPPLY. |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |