| 2005-07-06 00:00:00 | ************ UNSAT2ND REVIEW ********* |
| | |
| | PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED. |
| | |
| | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH PANEL |
| | SCHEDULE(S). PLEASE SEE 700.12E FOR |
| | EM/EXT LTS. |
| | 215.5 |
| | |
| | 2)NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| | PLEASE SHOW PER |
| | 220.3,220.10,220.11,220.13 ETC. |
| | PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| | AT 125% PER 215.3,230.42 |
| | PLEASE SEE LOAD CALCULATIONS SUBMITTED |
| | ARE ONLY LOAD ON SUB PANEL. PLEASE ALSO |
| | SEE LOAD CALCULATIONS ARE FOR |
| | RESIDENTIAL USE. |
| | |
| | 2)NOTE: PLEASE SEE NEW MAIN DISCONNECT |
| | APPEARS TO BE SHOWN, HOWEVER NO |
| | INFORMATION IS PROVIDED FOR THIS. |
| | AIC RATING, VOLTAGE, AMPERAGE, GROUPING |
| | ETC |
| | 215.5,110.9,110.14,230.72 ETC |
| | PLEASE INDICATE CONDUCTORS FROM METER TO |
| | MAIN AND MAIN TO NEW SUB PANEL. |
| | 215.5,240.4,310.16,250.24,250.6 ETC. |
| | |
| | 3)NOTE: PLEASE SHOW LOCATION OF COND |
| | UNIT AND DISC'S REQUIRED FOR A/C CU AND |
| | AHU. 440.11 |
| | PLEASE ALSO SEE MISSING GFI RECEPT FOR |
| | CU. 210.63 |
| | |
| | PLEASE BE SURE TO SEE ANY POSSIBLE |
| | COMMENTS FROM OTHER REVIEWER(S) WHICH |
| | MAY AFFECT ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ANY AND ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | |
| | PLEASESUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |