| 2005-03-18 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FBC-2001 BUILDING |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | A) FOLLOWING COMMENTS WERE NOT ADDRESSED |
| | OR NOT ADDRESSED SUFFICIENTLY. THE |
| | COMMENT NUMBER SHALL STAY THE SAME TO |
| | AVOID CONFUSION. |
| | 1) SHTS IRR 1,2,&3 PRINTED NAME OF THE |
| | PERSON SEALING THE PLANS IS REQURED ON |
| | THE TITLE BLOCK. FAC 61G1-16.004(6) & FS |
| | 481.2055. RESPONSE NOTED "OUR DOCUMENTS |
| | DO NOT INCLUDE AN IRR SHEET SERIES". |
| | THERE ARE IRRIGATION SHEETS SUBMITTED. |
| | ALSO THE CERTIFICATE OF AUTHORIZTION IS |
| | REQUIRED FOR ALL IRR. SHEETS. THIS IS |
| | REQUIRED AS AN "AA" OR "AR" NUMBER AS |
| | THE SHEETS WERE SIGNED & SEALED BY A |
| | LANDSCAPE ARCHITECT. FS 481.219(2) |
| | 3) OIL WATER SEPARATOR SHALL BE SIZED |
| | AND APPROVED BY RODNEY COMPO, |
| | ENVIRONMENTAL COMPLIANCE. WASTE ORD |
| | #2938-96. (561) 837-4074 - RESPONSE |
| | NOTED, BUT SEE ATTACHED SHEET FROM |
| | RODNEY COMPO REQUIREING A 100 GAL OIL |
| | WATER SEPARATOR. SEPARATE PERMIT |
| | REQUIRED FOR SEPARATOR. |
| | 10) ALL SHEETS, TITLE BLOCK FOR |
| | ARCHITECT, THE COMPANY NAME IS NOT THE |
| | SAME AS SHOWN ON THE DBPR LICENSE SEARCH |
| | FOR THE CERTIFICATE OF AUTHORIZATION, |
| | PLEASE MAKE THE CORRECTION ON THE TITLE |
| | BLOCK, SHOW APPROIATE BUSINESS NAME. |
| | (SEE ATTACHED SHEET FROM DBPR WEBSITE). |
| | FAC 61G1-16.004 & FS 481.291 - ALL |
| | SHEETS FOR ARCHITECT AND ENGINEER, THE |
| | DATE THAT THE SEAL AND SIGNATURE IS |
| | AFFIXED SHALL BE ON THE SEAL. FAC |
| | 61G15-23.002(2) - FAC 61G1-16.003 / FS |
| | 471.025 - 481.2055. |
| | 11) SUBMIT CALCULATIONS FOR MINIMUM |
| | FACILITIES FOR FIXTURES. 2 DRINKING |
| | FOUNTAINS ARE REQUIRED. SHT TO-1 |
| | INDICATES A DRINKING FOUNTAIN IN LOBBY |
| | AREA, BUT NO DRINKING FOUNTAIN IS SHOWN |
| | ON THE FLOOR PLAN, NOR ON THE SANT. OR |
| | WATER PIPING RISERS. ONLY ONE WATER |
| | COOLER IS SHOWN. |
| | 13) SHT PE.1 WATER RISER ISOMETRIC SHALL |
| | SHOW FULL OPEN VALVES ON ALL EVER WATER |
| | DOWN-FEED WATER LINE. SECTION 606.1(4) |
| | ALL WATER HAMMER ARRESTORS SHALL BE |
| | LOCATED NEAR THE FIXTURES IN AN |
| | "EFFECTIVE RANGE" NOT IN THE CEILING AS |
| | SHOWN. PDI-WH 201 & MANUF. INSTALL. |
| | INSTRUCTIONS. |
| | 15) A SEPARATE GAS PERMIT IS REQUIRED, |
| | AND THE FOLLOWING INFORMATION IS |
| | REQUIRED TO ISSUE THE GAS PERMIT: |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. - NOT ALL LENGTHS ARE |
| | SHOWN ON THE ISOMETRIC. SHOW LOCATION OF |
| | METER AND ALL MEASURMENTS TO METER. |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). - THIS WAS |
| | NOT SHOWN ON THE PLANS. |
| | G. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. - |
| | IF THE GAS DELIVERY PRESSURE IS .5 PSI, |
| | DELETE ALL SECONDARY REGULATORS FROM THE |
| | ISOMETRIC AS THEY WILL NOT BE IN SYSTEM. |
| | ALL SHUT OFF VALVES SHALL BE LOCATE |
| | MAXIMUM OF 6' FROM GAS APPLIANCE. |
| | SECTION 409.7. SOME ARE SHOWN EXCEEDING |
| | THIS REQUIREMENT ON THE ISOMETRIC. |
| | H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2. - NO |
| | SHEETS WERE FOUND. |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION.- |
| | THE SHEETS THAT WERE VOIDED WERE NOT |
| | REMOVED FROM THE SETS OF PLANS. REMOVE |
| | ALL OLD SHEET AND SUBMIT ONE SET OF OLD |
| | SHEETS FOR COMPARISON. - ONE SET OF |
| | PLANS SUBMITTED FOR REVIEW WAS SUBMITTED |
| | AS LOOSE SHEETS. PLEASE SUBMIT TWO OR |
| | MORE SETS OF PLANS FOR REVIEW. SECTION |
| | 104.2.1. |
| | **************NEW COMMENT*************** |
| | 1B) THE FOLLOWING SHEETS ARE NOT SHOWN |
| | ON THE DRAWING INDEX, BUT WERE INCLUDED |
| | IN THE SETS OF PLANS. SHEETS 1 THRU 11 |
| | OF 11, SHEET 1 OF 1, L1 & L2, IRR 1,2,3 |
| | PH-1, E1 OF 2, E1 OF 6. CORRELATE THE |
| | INDEX SHEET WITH SHEETS SUBMITTED. |
| | SECTION 104.2.1. |