| Plan Review Notes For Permit 05010365 |
| Permit Number |
05010365 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-03-29 00:00:00 | DENIED | | | | | | 1) PLANS SHOW AN ACCESS GATE INTO THE | | | PROPERTY. PLEASE INCLUDE THE WIDTH | | | DIMENSION WHICH SHALL BE A MINIMUM OF 20 | | | FEET FOR EMERGENCY VEHICLES. | | | | | | 2) A KNOX KEY ENTRY WILL BE PROVIDED. | | | WHAT WILL SERVE AS THE BACK UP IN THE | | | EVENT OF POWER FAILURE? | | | | | | 3) PLEASE SHOW THE LOCATION OF FIRE | | | HYDRANTS. BE ADVISED THAT A FIRE HYDRANT | | | MUST BE LOCATED NOT FURTHER THAN 150 | | | FEET FROM THE CLOSEST HYDRANT. | | | | | | 4) PLEASE BE ADVISED THAT AN ADDRESS | | | NUMBER IS REQUIRED ON THE BUILDING. THE | | | NUMBERS SHALL BE AT LEAST 6" IN HEIGHT | | | AND CONTRASTING TO THE BACKGROUND. | | | | | | 5) SEPARATE SHOP DRAWINGS AND PERMITS | | | WILL BE REQUIRED FOR THE FIRE SPRINKLER | | | AND FIRE ALARM SYSTEMS. | | | | | | 6) THE FIRE SPRINKLER SYSTEM SHALL BE | | | MONITORED BY A U.L. LISTED CENTRAL | | | STATION SERVICE. | | | | | | | | | MIKE WENNERGREN, A/CAPTAIN | | | WPBFR(561) 835-2910 |
|