| 2005-03-08 00:00:00 | ********* UNSAT 2ND REVIEW ********* |
| | |
| | PLEASE SEE PLANS ARE STILL ONLY IN FOR |
| | PLAN REVIEW AND HAVE NOT BEEN SUBMITTED |
| | FOR PERMIT. |
| | |
| | |
| | PLEASE SEE SOME NOTES FROM FIRST REVIEW |
| | STILL NEED TO BE ADDRESSED. |
| | |
| | 1)NOTE: NOTE #1 NO, PLEASE INCLUDE ALL |
| | REQUIRED LICENSE INFORMATION ON TITLE |
| | BLOCKS FOR ALL TRADES AND FOR ALL SHEETS |
| | AS REQUIRED UNDER FS 481.219,471.023 |
| | FAC 61G1-16.004,61G15-23.002. |
| | PLEASE SEE ATTACHED SHEETS FROM STATE |
| | DBPR SITE PERTAINING TO FIRM SHOWN ON |
| | PLANS. |
| | THIS FIRM IS SHOWN AS "APPLICANT" AT |
| | THIS TIME. |
| | PLEASE SEE ALL TITLE BLOCKS. PH-SHEETS |
| | ETC. |
| | PLEASE ALSO BE AWARE, FIRM # SHOWN ON |
| | PLANS AT THIS TIME APPEAR TO BELONG TO A |
| | DIFFERENT FIRM. |
| | PLEASE ALSO BE AWARE, FIRM NAME AS |
| | REGISTERED WITH STATE MUST BE THE SAME |
| | AS ON TITLE BLOCK. |
| | PLEASE SEE THIS IS REQUIRED OF ALL |
| | SHEETS AND TRADES WHEATHER OR NOT |
| | COMMENT IS MADE BY OTHER REVIEWER(S). |
| | |
| | 2)NOTE: NOTE #2, NO, PLEASE SEE SOME |
| | SHEETS SEAL IS NOT CLEARLY VISABLE WITH |
| | INFORMATION REQUIRED. PLEASE SEE FS |
| | 471.025 FOR ENGINEERS AND 481.221 FOR |
| | ARCH'S. |
| | PLEASE ALSO SEE PLANS MUST BE SIGNED, |
| | "DATED " AND SEALED. |
| | LTR FROM ENGINEER MR. JAMES FOX WAS |
| | RECIEVED AND PLACED IN FILE FOR |
| | SIGNATURE VERIFICATION. |
| | |
| | 3)NOTE:NOTE #3, OK, BLDG TO REVIEW WIND |
| | LOAD CALCULATIONS. |
| | |
| | 4)NOTE: NOTE #4 NO, PLEASE SEE CWP AND |
| | GRND ROD WAS ADDED, HOWEVER FOOTER |
| | STEEL, WAS NOT SHOWN. PLEASE SEE PLANS |
| | REFERENCE 250.50 FOR GES. PLEASE SEE FBC |
| | 104.2.1, PLANS SHALL NOT CONTAIN |
| | REFERENCE TO TECHNICAL CODES IN WHOLE OR |
| | IN PART. |
| | |
| | 5)NOTE: NOTE #5, OK, NOT SHOWN PER |
| | DETAIL NEC ARTICLES, HOWEVER ALL LOADS |
| | ARE SHOWN AS CONNECTED LOAD W/OUT |
| | DERATING. THIS IS OK. |
| | |
| | 6)NOTE: NOTE #6, NO, PLEASE SEE PREVIOUS |
| | COMMENT WAS NOT TO CHANGE IDENTIFICATION |
| | OF MDP TO MCB. IT WAS TO REQUIRE A MCB, |
| | (MAIN CIRCUIT BREAKER). |
| | PLEASE SEE MAIN IS SHOWN AS PART OF A |
| | PANEL BOARD FOR SERVICE WHICH WILL |
| | CONTAIN MORE THAN 6-SPACES FOR MEANS OF |
| | DISC OF SERVICE. PLEASE SEE THAT A MCB |
| | WILL BE REQUIRED.230.71A, 240.4 |
| | |
| | |
| | 7)NOTE: NOTE #7 OK. |
| | |
| | |
| | PLEASE SEE POSSIBLE COMMENTS FROM OTHER |
| | REVIEWER(S) WHICH MAY AFFECT ELECTRICLA |
| | PLANS. |
| | |
| | PLEASE REMOVE ALL OLD SHEETS AND INSERT |
| | NEW REVISED SHEETS INTO COMPLETE SETS |
| | FOR REVIEW AND STAMPING. |
| | PLEASE SEE ALL SHEETS WERE LOOSE IN |
| | ROLLS? |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |