| Date |
Text |
| 2005-02-03 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FBC-2001 BUILDING |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) SHTS IRR 1, 2, & 3 PRINTED NAME OF |
| | THE OF THE PERSON SEALING THE PLANS IS |
| | REQUIRED ON THE TITLE BLOCK. FAC |
| | 61G1-16.004(6) & FS 481.2055 |
| | 2) SHT IRR 3 POINT OF CONNECTION, |
| | (POC), |
| | STATES 2" WATER METER. CIVIL SHEET 8 OF |
| | 11 INDICATES 1" TAP. PLEASE CLARIFY. |
| | SECTION 104.2.1. |
| | 3) OIL WATER SEPARATOR SHALL BE SIZED |
| | AND APPROVED BY RODNEY COMPO, |
| | ENVIRONMENTAL COMPLIANCE. WASTE ORD. |
| | NO. |
| | 2938-96. (561)837-4074. |
| | 4) SHTS F1.1 & A8.2 CLEAR FLOOR SPACE |
| | FOR WATER CLOSETS AND URINAL ARE |
| | REQUIRED IN THE MENS TOILET ROOM. ALSO |
| | SHOW THE TURNING ARE IN THE TOILET ROOM |
| | NOT THE ACCESSIBLE STALL. - CLEAR FLOOR |
| | SPACE FOR THE WATER CLOSET IS REQUIRED |
| | IN THE WOMENS TOILET ROOM, WITH THE |
| | TURNING AREA SHOWN IN THE TOILET ROOM |
| | NOT THE ACCESSIBLE STALL. SECTIONS |
| | 11-4.16.2, 11-4.18.3 & 11-4.22.3- |
| | ALSO |
| | SHOW THE CLEAR FLOOR SPACE FOR THE W/C |
| | IN ROOM #106, THE CLEAR FLOOR SPACE FOR |
| | THE BREAK ROOM SINK IN ROOM #115, |
| | (FORWARD APPROACH IS REQUIRED - MAX. |
| | 19" |
| | UNDERNEATH THE SINK), 11-4.24.5. |
| | 5) SHTS F1.1 & A8.2 BREAK ROOM SINK |
| | MODEL #CR-25-21 INDICATES A 7" DEEP |
| | SINK, BUT SECTION 11-4.24.4 STATES THAT |
| | 6-1/2" IS THE MAXIMUM DEPTH. ALSO |
| | FAUCET |
| | SHALL BE LEVER OPERATED, PUSH TYPE, |
| | TOUCH TYPE, OR ELECTRONICALLY |
| | CONTROLLED. SECTION 11-4.24.7 |
| | 6) SHT A1.2 ROOM FINISH SCHEDULE, MORE |
| | INFORMATION FOR WB-1 & WB-2 SHOWN FOR |
| | THE BASE. INDICATE MATERIAL TYPE. PER |
| | SECTION 1204.2 MATERIAL SHALL BE NOT |
| | ABSORBENT. PLEASE CLARIFY. |
| | 7) SHT A1.2 ROOM FINISH NOTE #3. |
| | INDICATE THAT WAINSCOT IS REQUIRED. |
| | SECTION 104.2.1. & SECTION 1204.2. |
| | 8) SHT A2.1 SUBMIT CALCULATIONS FOR |
| | ROOF |
| | DRAINS PER SECTIONS 1106 & 1107 AND ALL |
| | SUBSECTIONS. SHOW TOTAL AREA OF THE |
| | ROOF |
| | AND SHOW 1/2 AREA OF ALL VERTICAL WALLS |
| | INCLUDING PARAPETS. INDICATE THE AREA |
| | OF |
| | THE ROOF THAT DRAINS TO EACH DOWNSPOUT. |
| | SHOW SIZE OF GUTTERS PER TABLE 1106.6, |
| | INDICATE SLOPE OF GUTTERS AND SHOW THE |
| | HIGH POINT OF THE GUTTER. |
| | 9) SHT A8.1 DETAIL #2 SHOW KNEE |
| | CLEARANCE 11-4.23.3, ACCESSIBLE WATER |
| | CLOSET SHOW HEIGHT 11-4.16.3, |
| | ACCESSIBLE |
| | URINAL SHOW HEIGHT 11-4.18.2, CLEAR |
| | FLOOR SPACE 11-4.18.3. |
| | 10) ALL SHEETS, TITLE BLOCK FOR |
| | ARCHITECT, THE COMPANY NAME IS NOT THE |
| | SAME AS SHOWN ON DBPR LICENSE SEARCH |
| | FOR |
| | THE CERTIFICATE OF AUTHORIZATION. |
| | PLEASE |
| | MAKE THE CORRECTION ON THE TITLE BLOCK. |
| | SHOW APPROIATE BUSINESS NAME. FAC |
| | 61G1-16.004 & FS 481.291. - AN ENGINEER |
| | SHALL SIGN HIS NAME AND AFFIX HIS SEAL |
| | TO ALL PLANS. INITIALS ARE NOT |
| | ACCEPTABLE. THE DATE THAT THE SIGNATURE |
| | AND SEAL IS AFFIXED SHALL BE ENTERED ON |
| | THE PLANS IMMEDIATELY UNDER THE |
| | SIGNATURE OF THE PROFESSIONAL ENGINEER. |
| | FAC 61G15-23.002(1) & FS 471.025 |
| | 11) SUBMIT CALCULATIONS FOR MINIMUM |
| | FACILITIES FOR FIXTURES. INDICATE ON |
| | PLANS THE SQUARE FOOTAGE FOR EACH |
| | OCCUPANCY. TABLES 1003.1 & 403.1. |
| | 12) SHT P2.1 HOUSE TRAP NOT APPROVED. |
| | DELETE FROM DETAIL "B". SECTION 1002.1 |
| | 12) SHT P3.1 ALL RISER DIAGRAMS SHALL |
| | BE |
| | IN ISOMETRIC FORM AND SHALL REFLECT THE |
| | FLOOR PLAN. SECTION 104.2.1. |
| | 13) SHT P3.1 WATER RISER ISOMETRIC |
| | SHALL |
| | SHOW VALVES REQUIRED BY SECTION |
| | 606.1(4) |
| | FULL OPEN VALVES ON EVERY DOWN-FEED |
| | WATER LINE, AND SHOW THE LOCATION OF |
| | ALL |
| | WATER HAMMER ARRESTORS REQUIRED BY |
| | SECTION 604.9 AND SHALL BE LOCATED NEAR |
| | THE FIXTURE, IN AN "EFFECTIVE RANGE" |
| | NOT |
| | IN THE CEILING AS SHOWN. PDI-WH 201 AND |
| | MANUF. INSTALLATION INSTRUCTIONS. |
| | 14) SHT P3.1 INSPECTION BAY WASTE & |
| | VENT |
| | INDICATES A VERTICAL VENT FOR THE 4" |
| | FD-3 ON RISER DIAGRAM, BUT ON SHT P2.1 |
| | THE VENT IS INDICATED AS A HORIZONTAL |
| | DRY VENT WHICH IS NOT APPROVED PER |
| | SECTION 905.3 & 905.4 PLEASE CLARIFY. |
| | 15) A SEPARATE GAS PERMIT IS REQUIRED, |
| | AND THE FOLLOWING INFORMATION IS |
| | REQUIRED TO ISSUE THE GAS PERMIT: |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING |
| | USED. |
| | C. TYPE OF GAS, (LP OR NATURAL) |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM |
| | PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | F. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| | GAS CODE SECTION 304. |
| | G. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | H. SUBMIT MANUFACTURE SHEETS FOR ALL |
| | GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | I. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY |
| | LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, |
| | BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | J. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK |
| | AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | K) INDICATE TYPE OF MATERIAL FOR |
| | REGULATOR VENTS. VENT MATERIAL SHALL BE |
| | NON COMBUSTABLE. SECTION 631.15 |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT |
| | NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE |
| | FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |