| 2005-01-26 00:00:00 | DENIED: |
| | 1.PLEASE PROVIDE OUTSIDE AIR |
| | CALCULATIONS PER 2001 FBC(M) TABLE |
| | 403.3.PLEASE INCLUDE OFFICE AREAS AS |
| | WELL AS THE GARAGE AREAS. |
| | |
| | 2.IT IS THE DETERMINATION OF THE |
| | BUILDING OFFICAL SINCE THIS IS NOT |
| | CLASSIFIED AS A "REPAIR GARAGE" AND |
| | SINCE CARS WILL BE MOVED IN AND OUT, |
| | THAT IT SHALL BE CLASSIFIED AS A |
| | "PARKING GARAGE".PLEASE SHOW |
| | COMPLIANCE WITH THE 2001 FBC 411.4.2. |
| | |
| | 3.PLEASE REFERENCE COMMENTS BY |
| | ELECTRICAL & BUILDING ON THE SIGNATURER, |
| | TITLE BLOCK AND CERTIFICATE OF |
| | AUTHORIZATION FOR THE ARCHITECTURAL & |
| | ENGINEERING FIRMS (FS 471.023, 471.025 & |
| | 481.219). |
| | |
| | 4.PLEASE NOTE, PLAN SHEET M2.1 |
| | INDICATES GAS FIRED HEATERS AS WELL |
| | HORIZONTAL UNIT HEATER (ELECTRIC). |
| | PLEASE CLARIFY THE PURPOSE OF THE |
| | ELECTRIC HEATER IN THE MECHANICAL ROOM. |
| | |
| | |
| | 5.PROVIDE COMBUSTION AIR CALCULATIONS |
| | FOR THE GHUH INDICATED ON PLAN SHEETS |
| | M2.1 & M7.1. |
| | |
| | 6.PLEASE PROVIDE MANUFACTURER |
| | SUBMITTAL DATA FOR ALL MECHANICAL |
| | EQUIPMENT. |
| | |