2005-01-13 00:00:00************* UNSAT *****************
  
 1)NOTE: PLEASE SEE MISSING INFORMATION
 REQUIRED ON TITLE BLOCK PER FAC
 61G15-23.002 AND FS 471.023
 PLEASE ALSO SEE ENGINEER IS REQUIRED TO
 SIGN PLANS WITH FULL SIGNATURE AS ON
 RECORD.
 FS 471.025
 PLEASE ALSO SEE NOTES FROM OTHER
 REVIEWERS FOR "STATE PLANS" THESE ARE
 PHOTOCOPIES.
  
 2)NOTE: PLEASE SHOW CIRCUITING ON PLANS
 AND CORRELATE WITH A SUBMITTED PANEL
 SCHEDULE.
 PLEASE SEE 700.12E FOR EM/EXT LTS.
  
 3)NOTE; PLEASE SUBMIT A LOAD CALCULATION
 FOR LOAD ADDED TO EXISTING "BUS" PANEL.
 215.5
  
 4)NOTE: PLEASE INCLUDE GROUNDING OF
 DETACHED BLDG PER 250.32
  
 5)NOTE: PLEASE VERIFY SIZE OF OCP FOR
 FEED TO NEW BLDG.
  
 PLEASE SEE POSSIBLE NOTES FROM OTHER
 REVIEWER(S).
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]