| Plan Review Notes For Permit 05010297 |
| Permit Number |
05010297 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-01-13 00:00:00 | ************* UNSAT ***************** | | | | | | 1)NOTE: PLEASE SEE MISSING INFORMATION | | | REQUIRED ON TITLE BLOCK PER FAC | | | 61G15-23.002 AND FS 471.023 | | | PLEASE ALSO SEE ENGINEER IS REQUIRED TO | | | SIGN PLANS WITH FULL SIGNATURE AS ON | | | RECORD. | | | FS 471.025 | | | PLEASE ALSO SEE NOTES FROM OTHER | | | REVIEWERS FOR "STATE PLANS" THESE ARE | | | PHOTOCOPIES. | | | | | | 2)NOTE: PLEASE SHOW CIRCUITING ON PLANS | | | AND CORRELATE WITH A SUBMITTED PANEL | | | SCHEDULE. | | | PLEASE SEE 700.12E FOR EM/EXT LTS. | | | | | | 3)NOTE; PLEASE SUBMIT A LOAD CALCULATION | | | FOR LOAD ADDED TO EXISTING "BUS" PANEL. | | | 215.5 | | | | | | 4)NOTE: PLEASE INCLUDE GROUNDING OF | | | DETACHED BLDG PER 250.32 | | | | | | 5)NOTE: PLEASE VERIFY SIZE OF OCP FOR | | | FEED TO NEW BLDG. | | | | | | PLEASE SEE POSSIBLE NOTES FROM OTHER | | | REVIEWER(S). | | | | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|