| Plan Review Notes For Permit 05010276 |
| Permit Number |
05010276 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-02-08 00:00:00 | 1. WRONG LIFE SAFETY CODE REFERENCED. | | | SHOULD READ 2003 EDITION. | | | | | | 2. DEMOLITION, RENOVATION, AND | | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | | | 3. DEBRIS SHALL BE REMOVED FROM THE | | | SITE DAILY. | | | | | | 4. NON-FIRE RATED VISQUEEN SHALL NOT | | | BE USED. | | | | | | 5. SEPARATE PLANS AND PERMITS REQUIRED | | | FOR ANY FIRE SPRINKLER REMODEL. | | | | | | 6. SEPARATE PLANS FOR ANY FIRE ALARM | | | EQUIPMENT. | | | | | | 7. PLEASE SHOW EXIT SIGNS AND | | | EMERGENCY LIGHTS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|