Plan Review Notes
Plan Review Notes For Permit 05010276
Permit Number 05010276
Review Stop B
Sequence Number 1
Notes
Date Text
2005-01-21 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05010276
 ADD: 777 S. FLAGLER # 1700 W
 CONT:GOODWIN CONTRACTORS
 TEL: (561)566-7623
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
 2)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 3) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 4) SHEET A0-0 THE COVER PAGE LIST THE
 HIGH RISE AS A TYPE IV BUILD WHEN IT
 SHOULD BE TYPEII.
  
 5) 609.2.1 PARTITIONS SHALL BE
 CONSTRUCTED OF NONCOMBUSTIBLE
 MATERIALS.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026