Plan Review Notes
Plan Review Notes For Permit 05010254
Permit Number 05010254
Review Stop B
Sequence Number 1
Notes
Date Text
2005-01-07 00:00:00BUIDING PLAN REVIEW : FAILED
  
 1. PLANS SHOW THE BUILDING IS A 4 UNIT
 2 STORY BUILDING.THE SURVEY SUBMITTED
 STATES IT IS A SINGLE FAMILY RESIDENCE.
 THE SURVEY IS NOT DATED OR SEALED.
  
 2. THE WINDOWS TO BE INSTALLED ARE NOT
 IMPACT RATED. ACCORDING TO THE
 IMPLEMENTATION STANDARD FOR HURRICANE
 MISSLE IMPACT PROTECTION REVISED AND
 EFFECTIVE SEPT. 23, 2004. #14 OF THE
 MISSLE IMPACT PROTECTION STANDARD
 STATES REMOVABLE STORM PANELS CAN NOT
 BE INSTALLED ON THE 2ND FLOOR OF A
 MULTI
 FAMILY UNIT. THE WINDOWS MUST BE IMPACT
 WINDOWS ABOVE THE FIRST FLOOR. A COPY
 OF THE POLICY IS ATTACHED FOR YOUR
 INFORMATION.
  
 3. THERE WERE NO FLORIDA PRODUCT
 APPROVALS SUBMITTED FOR THE DOORS,
 WINDOWS, MULLIONS & STORM PANELS.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE
 WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 WWW.FLORIDABUILDING.ORG
  
 4. THE EXTERIOR DOORS ACCORDING TO THE
 PRODUCT APPROVAL ARE NOT IMPACT RATED.
 THESE DOORS MUST MEET THE MEANS OF
 EGRESS. THEY SHOULD BE IMPACT RATED.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713