| 2005-01-07 00:00:00 | BUIDING PLAN REVIEW : FAILED |
| | |
| | 1. PLANS SHOW THE BUILDING IS A 4 UNIT |
| | 2 STORY BUILDING.THE SURVEY SUBMITTED |
| | STATES IT IS A SINGLE FAMILY RESIDENCE. |
| | THE SURVEY IS NOT DATED OR SEALED. |
| | |
| | 2. THE WINDOWS TO BE INSTALLED ARE NOT |
| | IMPACT RATED. ACCORDING TO THE |
| | IMPLEMENTATION STANDARD FOR HURRICANE |
| | MISSLE IMPACT PROTECTION REVISED AND |
| | EFFECTIVE SEPT. 23, 2004. #14 OF THE |
| | MISSLE IMPACT PROTECTION STANDARD |
| | STATES REMOVABLE STORM PANELS CAN NOT |
| | BE INSTALLED ON THE 2ND FLOOR OF A |
| | MULTI |
| | FAMILY UNIT. THE WINDOWS MUST BE IMPACT |
| | WINDOWS ABOVE THE FIRST FLOOR. A COPY |
| | OF THE POLICY IS ATTACHED FOR YOUR |
| | INFORMATION. |
| | |
| | 3. THERE WERE NO FLORIDA PRODUCT |
| | APPROVALS SUBMITTED FOR THE DOORS, |
| | WINDOWS, MULLIONS & STORM PANELS. |
| | |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, |
| | 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE |
| | WEBSITE |
| | AT WWW.FLORIDABUILDING.ORG. PRODUCTS |
| | WITH STATEWIDE APPROVAL ARE REQUIRED TO |
| | BE SUBMITTED WITH A COVER SHEET THAT |
| | LISTS THE PRODUCT IDENTITY NUMBER FROM |
| | THE STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 4. THE EXTERIOR DOORS ACCORDING TO THE |
| | PRODUCT APPROVAL ARE NOT IMPACT RATED. |
| | THESE DOORS MUST MEET THE MEANS OF |
| | EGRESS. THEY SHOULD BE IMPACT RATED. |
| | |
| | ANY QUESTIONS PLEASE CALL: |