2005-06-02 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
  
 1. APPLICATION DESCRIPTION OF PROJECT
 STATES "ERECTING A 2 STORY OUTDOOR
 PORCH", BUT PLANS INDICATE REMODEL OF
 SECOND FLOOR ON SHEET 2. ALSO INDICATED
 ON SHEET 2 OF THE PLANS IS A NEW TUB TO
 BE INSTALLED IN THE MASTER BEDROOM, AND
 A NEW SHOWER IN THE MASTER BATHROOM.
 THIS IS NOT INDICATED ON THE PERMIT
 APPLICATION. PLEASE CLARIFY. SECTION
 104.1.5.
 2. SHT 2 THE NEW TUB ADDED TO THE MASTER
 BEDROOM IS NOT INDICATED ON THE SANITARY
 RISER DIAGRAM. SECTION 104.2.1.
 3. PLEASE SUBMIT AN EXISTING SECOND
 FLOOR PLAN TO INDICATE WHAT REMODELING
 IS BEING DONE ON THE FLOOR. SECTION
 104.2.1.
 4. A SEPARATE PLUMBING PERMIT IS
 REQUIRED. SECTION 104.1.1.
  