| Plan Review Notes For Permit 05010253 |
| Permit Number |
05010253 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-06-02 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | | | | 1. APPLICATION DESCRIPTION OF PROJECT | | | STATES "ERECTING A 2 STORY OUTDOOR | | | PORCH", BUT PLANS INDICATE REMODEL OF | | | SECOND FLOOR ON SHEET 2. ALSO INDICATED | | | ON SHEET 2 OF THE PLANS IS A NEW TUB TO | | | BE INSTALLED IN THE MASTER BEDROOM, AND | | | A NEW SHOWER IN THE MASTER BATHROOM. | | | THIS IS NOT INDICATED ON THE PERMIT | | | APPLICATION. PLEASE CLARIFY. SECTION | | | 104.1.5. | | | 2. SHT 2 THE NEW TUB ADDED TO THE MASTER | | | BEDROOM IS NOT INDICATED ON THE SANITARY | | | RISER DIAGRAM. SECTION 104.2.1. | | | 3. PLEASE SUBMIT AN EXISTING SECOND | | | FLOOR PLAN TO INDICATE WHAT REMODELING | | | IS BEING DONE ON THE FLOOR. SECTION | | | 104.2.1. | | | 4. A SEPARATE PLUMBING PERMIT IS | | | REQUIRED. SECTION 104.1.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|