2005-06-02 00:00:00DENIED:
 PLAN SHEET 2 OF 2 INDICATES A BATHROOM
 OUTSIDE OF THE MASTER BEDROOM WITH A
 NOTE; "TO REPLACE WINDOW IN BATH WITH A
 24" X 24" SH TEMP GLASS FROSTED", PER
 2001 FBC/M 402.3.1 ROOMS CONTAINING
 BATHTUBS, SHOWERES, SPACES & SIMILAR
 BATHING FIXTURES SHALL BE MECHANICALLY
 VENTILATED UNLESS THEY HAVE WINDOWS WITH
 NO LESS THAN 3 SQ FT OF OPEN AREA.
  
 PLEASE SHOW COMPLIANCE IN ALL AREAS THAT
 PERTAIN TO THIS CODE SECTION.
  
 PLEASE NOTE, APPLICATION DOES NOT
 INDICATE ANY INTERIOR WORK BEING DONE,
 BUT THE PLANS INDICATE PLUMBING WORK AND
 DUE TO THE CHANGING OF THE WINDOW, NEW
 SHOWER, CLAW TUB, MECHANICAL, PLUMBING
 AND ELECTRICAL PERMITS WILL BE REQUIRED.
  