Plan Review Notes
Plan Review Notes For Permit 05010245
Permit Number 05010245
Review Stop E
Sequence Number 2
Notes
Date Text
2005-04-11 00:00:00******* UNSAT *******
  
 1)NOTE: PLEASE SEE 210.52C1 FOR MISSING
 RECEPTS MISSING ALONG KITCHEN
 COUNTERSPACE.
  
 2)NOTE: PLEASE SEE 210.8A6, "ALL"
 RECEPTS SERVING KITCHEN COUNTERSPACE ARE
 REQUIRED TO BE GFI/GFI PROTECTED.
  
 3)NOTE: PLEASE SEE
 210.8,210.52D,210.11C3, BATH RECEPTS TO
 BE 20A AND #12, AND GFI
  
 4)NOTE: PLEASE SEE THE ABOVE THREE
 COMMENTS WERE ON THE FIRST REVIEW AND
 NONE OF THESECHANGES WERE MADE TO THE
 PLANS?
 PLEASE NOW SEE RESPONSE LETTER FROM MR
 ROBERT BELL (ARCHITECT) MENTIONS:
 "KITCHEN IS EXISTING AND WILL REMAIN
 UNCHANGED".
 PLEASE CLARIFY THIS AS PERMIT
 APPLICATION DOES NOT CORRELATE WITH
 THIS.
 PERMIT APPLICATION MENTIONS TO "GUT AND
 REMODEL KITCHEN".
  
 5)NOTE: PLEASE SUBMIT PLANS WHICH WILL
 CORRELATE WITH SCOPE OF WORK BEING
 APPLIED FOR. PLEASE SEE ABOVE FIRST
 THREE COMMENTS IF INDEED WORK IS BEING
 DONE IN KITCHEN AND BATH.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  