| Plan Review Notes For Permit 05010245 |
| Permit Number |
05010245 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-01-18 00:00:00 | ************** UNSAT ****************** | | | | | | PLEASE SEE PLANS ARE ONLY IN FOR PLAN | | | REVIEW NAD NOT FOR PERMIT. | | | | | | 1)NOTE: PLEASE SEE 210.52C1 FOR KITCHEN | | | COUNTERSPACE RECEPT SPACING. | | | | | | 2)NOTE: PLEASE SHOW ALL RECEPTS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI | | | PROTECTED. | | | | | | 3)NOTE: PLEASE SHOW BATH GFI'S AS GFI | | | PER 210.8, ALSO MUST NOTE AS 20A, #12, | | | PER 210.11C3 | | | | | | PLEASE SEE THESE ITEMS COULD BE | | | REDLINED, HOWEVER PLANS ARE ONLY IN FOR | | | "PLAN REVIEW". | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|