| Plan Review Notes For Permit 05010235 |
| Permit Number |
05010235 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-01-18 00:00:00 | *********** UNSAT **************** | | | | | | 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | | SHOWING ALL EXISTING AND NEW LOADS ADDED | | | TO SERVICE. | | | 215.5,220.31B | | | PLEASE SEE ALL CONTINOUS LOADS ARE TO BE | | | SHOWN AT 125%. PUMP, HEAT PUMP,,, | | | | | | **** NOTE**** | | | ALL PLANS/DRAWINGS MUST CONTAIN THE | | | PRINTED NAME AND SIGNATURE OF PERSON | | | RESPONSIBLE FOR PLANS. FBC 104.2.1 | | | | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|