Plan Review Notes
Plan Review Notes For Permit 05010234
Permit Number 05010234
Review Stop P
Sequence Number 1
Notes
Date Text
2005-01-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A-1 NOTE STATES "DRAWING
 SUBMITTED FOR INFORMATION ONLY.
 DEMOLITION PERMIT HAS ALREADY BEEN
 APPLIED FOR BY CONTRACTOR". INFORMATION
 FROM CONTRACTOR WITH DEMO PERMIT
 INDICATES THAT THE DEMO PERMIT WILL BE
 VOIDED, AND THAT THEY WILL NOT BE DOING
 THE DEMOLITION. - THE VALUE OF THE
 APPLICATION WILL BE ADJUSTED FOR THE
 DEMOLITION AND THE APPLICATION AND
 PERMIT WILL HAVE TO REFLECT THE DEMO
 WORK, SECTION 104.2.1. NEW DEMO PLAN
 REQUIRED. SECTION.
 2) SUBMIT A WATER RISER DIAGRAM. SHOW
 ALL PIPE SIZES AND WHERE REQUIRED BY
 SECTION 604.9 SHOW ANY WATER HAMMER
 ARRESTORS LOCATED NEAR THE FIXTURES IN
 AN "EFFECTIVE RANGE". PDI-WH 201.
 SECTION 104.3.1.1.
 3) SHT A-2 LOUNGE SINK DETAIL. THE
 FOLLOWING INFORMATION IS REQUIRED ON
 THE
 DETAIL TO SHOW COMPLIANCE WITH SECTION
 11-4.24 AND ALL SUBSECTIONS:
 A) KNEE CLEARANCE 11-4.24.3
 B) DEPTH OF SINK11-4.24.4
 C) CLEAR FLOOR SPACE 11-4.24.5 FORWARD
 APPROACH REQUIRED AND SHALL EXTEND A
 MAXIMUM OF 19" UNDER THE SINK.
 D) EXPOSED PIPES AND SURFACES
 11-4.24.6
 E) FAUCETS 11-4.24.7
 (NOTE: BUILDING OFFICIAL HAS DETERMINED
 THAT THERE ARE TO BE NO DOORS UNDER THE
 SINK IN THE CLEAR FLOOR SPACE)
 4) SHT A-2 SHOW THE CLEAR FLOOR SPACE
 FOR THE DRINKING FOUNTAIN PER SECTION
 11-4.15.5(1).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]