Plan Review Notes
Plan Review Notes For Permit 05010185
Permit Number 05010185
Review Stop M
Sequence Number 2
Notes
Date Text
2005-02-11 00:00:00DENIED:
 PLEASE NOTE, ON THE PREVIOUS REVIEW
 COMMENT #1 REQUESTED ENGINEERED
 DRAWINGS.THE PLANS SUBMITTED ARE FOR
 RISERS ONLY.PLEASE CLARIFY IF THE
 INTENT IS TO SUBMIT ENGINEERED PLANS AT
 A LATER DATE FOR THE LAYOUT OF THE DUCT
 SYSTEM AND THE PIPING?THE FOLLOWING
 INFORMATION IS ALSO REQUIRED.
  
 1.PLANS ONLY SIZE RISER.PLEASE
 INDICATE SIZE OF BRANCH LINES TO THE
 INDIVIDUAL FAN COILS.
  
 2.INDICATE WHAT MATERIAL BRANCH LINES
 WILL BE.
  
 3.PROVIDE TYPICAL DETAIL FOR FAN COIL
 INSTALLATION.PLEASE INDICATE ANY
 ISOLATION/SHUT OF VALVES, UNIONS, ETC.
 THAT MAY BE INSTALLED.
  
 4.PROVIDE INFORMATION ON THE AHU'S TO
 THE COMMON AREAS.INDICATE DUCT SMOKE
 DETECTORS.
  
 5.PERMIT APPLICATION INDICATES
 "DUCTWORK AS NEEDED".IT IS MY
 UNDERSTANDING THAT ALL DUCTWORK HAS BEEN
 REMOVED.PROVIDE DUCT LAYOUT, INDICATE
 DUCT SIZE AND MATERIAL.PLEASE NOTE,
 THIS DOES NOT HAVE TO BE SUBMITTED PRIOR
 TO PERMIT BEING ISSUED.PLANS WILL BE
 REQUIRED SO AS TO HAVE "LEGAL RECORD" AS
 TO THE WORK DONE.PLEASE INDICATE ALL
 FIRE DAMPERS AS REQUIRED PER 2001
 FBC(M)607.6.
  
 6.PROVIDE OUTSIDE AIR CALCULATIONS IN
 ACCORDANCE WITH 2001 FBC(M) TABLE 403.3.
  
 7.PLEASE NOTE, THE LETTER FROM SPEARS
 MANUFACTURING COMPANY IS ADDRESSED TO
 REY AND SON PLUMBING.CHILLED WATER
 SYSTEMS FOR HVAC IS NOT IN THE SCOPE OF
 WORK UNDER A PLUMBING CONTRACTORS
 LICENSE.
  
 8.THE LETTER FROM J-M MANUFACTURING IS
 SIGNED BY THE "PRODUCT ASSURANCE
 ENGINEER".PER THE FS 471.025 & THE FAC
 61G15-23.002 (1), A PROFESSIONAL
 ENGINEER SHALL AFFIX HIS SEAL TO ALL
 PLANS SPECIFICATIONS, REPORTS AND OTHER
 DOCUMENTS PREPARED OR ISSUED THAT ARE
 BEING FILED FOR PUBLIC RECORD.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.