Notes
Date Text
2005-01-06 00:00:00DENIED:
 1.REFERENCE FS 471, HVAC WORK THAT IS
 GREATER THAN $50,000, GREATER THAN 15
 TON SYSTEM WHICH IS DESIGNED TO
 ACCOMMODATE FOR THAN 100 PEOPLE, THIS
 WILL REQUIRE PLANS PREPARED BY A
 REGISTERED ENGINEER.
  
 2.PER FBC(M)1202.3, MATERIALS SHALL BE
 RATED FOR THE OPERATING TEMPERATURE &
 PRESSURE OF THE HYDRONIC SYSTEM.
 MATERIALS SHALL BE SUITABLE FOR THE TYPE
 OF FLUID IN THE HYDRONIC SYSTEM.
  
 3.PROVIDE MANUFACTURER'S SUBMITTAL
 DATA AND INSTALLATION INSTRUCTIONS
 APPLICABLE TO "LOW TEMPERATURE"
 INSTALLATIONS.
  
 4.PER 2001 AMENDMENTS TO THE FBC
 104.2.1.2, THE BUILDING OFFICIAL MAY
 REQUIRE DETAILS & COMPUTATIONS AND OTHER
 DATA NECESSARY TO ACCOUNT FOR THE
 INSTALLATION AND THE BASIS OF
 CALCULATIONS.ALL SPECIFICATIONS SHALL
 BE PREPARED BY AN ENGINEER OR
 ARCHITECT.
  
 5.PROVIDE SPECIFIC INFORMATION AS TO
 THE SCOPE OF WORK AND DESIGNATE NEW FROM
 EXISTING.
  
 6.PLEASE PROVIDE EQUIPMENT SCHEDULE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  