2005-01-25 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 NFPA 99
 NFPA 54
  
 1) MORE INFORMATION IS REQUIRED.
 INDICATE THE USE OF THE GASES. SECTION
 104.2.1.
 2) SHT PO.1 GENERAL GAS NOTES INDICATES
 THAT ALL GAS LINES SHALL BE 1/8" BUT
 THE
 FITTINGS SHALL BE 7/8" SWEAGLOCK.
 PLEASE
 CLARIFY. SECTION 104.2.1. (ALSO SEE SHT
 P5.1 RISER DIAGRAM SHOWS 1/2" PIPE).
 3) SHT P0.1 GENERAL GAS NOTES REFERENCES
 NFPA 54 WHICH IS FOR NATURAL GAS. PLEASE
 INDICATE WHERE THE NATURAL GAS SYSTEM IS
 LOCATED AND SHOW PIPING DIAGRAM FOR THIS
 SYSTEM. MORE COMMENTS MAY FOLLOW WITH
 THE RESPONSE FROM THIS COMMENT.
 4) INDICATE THE AMOUNT AND TYPE OF GAS
 STORED ON THE JOBSITE. SECTION 104.2.1.
 5) SHT P2.1 NOTES INDICATE (3) LINES
 FROM HELIUM, NITROGEN, AND ACETLYENE
 TANKS, - (2) LINES FROM ARGON AND
 NITROGEN TANKS, - (4) LINES FROM ARGON,
 BUT SHT P5.1 SHOWS 4 LINES, 1EA FROM
 ARGON, HELIUM, ACETYLENE, & NITROGEN TO
 EACH VALVE BOX. PLEASE CLARIFY.
 6) PLEASE INDICATE WHERE THE AIR AND
 CH4
 GAS IS PIPED TO. THIS IS NOT INDICATED
 ON THE PLANS. SECTION 104.2.1.
 7) SUBMIT MSDS SHEETS FOR ALL HAZARDOUS
 MATERIALS STORED AND/OR USED ON THE JOB
 SITE. SECTION 104.2.1.
 8) STH P5.1 SUBMIT A DETAIL FOR THE
 VENTING FOR THE GAS TANK STORAGE ROOM.
  