| 2005-01-21 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT:05010076 |
| | ADD: 1400 NORTHPOINT PKWY# 10 |
| | CONT: BRICAR ENTERPRISES |
| | TEL: (954)675-1976 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | |
| | 1)FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | THE NEW LAB DOESN'T INDICATE IF THERE |
| | WILL BE FUME HOODS? WHAT QUANITIES OF |
| | GASSES WILL BE STORED? |
| | |
| | 2) ALSO THE PLUMBING PAGES INDICATE THE |
| | USE OF HYDROGEN TANKS IN A INCLOSURE |
| | BUT THERE IS NO MENTION OF PIPING OF |
| | HYDROGEN? |
| | |
| | 3)THE ENCLOSURE HOLDING THE HYDROGEN |
| | TANK WHAT IS IT RATED FOR? |
| | |
| | 4) 1511.7 ROOF MOUNTED MECHANICAL UNITS |
| | SHALL BE MOUNTED ON CURBS RAISED A |
| | MINIMUM OF 8 INCHES ABOVE THE ROOF SUR- |
| | FACE, OR WHERE ROOFING MATERIALS EXTEND |
| | BENEATH THE UNIT, ON RAISED EQUIPMENT |
| | SUPPORTS PROVIDING A MINIMUM CLEARENCE |
| | HEIGHT IN ACCORDANCE WITH TABLE 1511.7. |
| | MECH. 301.13 WIND RESISTANCE MECHANICAL |
| | EQUIPMENT, APPLIANCES AND SUP PORTS THAT |
| | ARE EXPOSED TO WIND SHALL BE DESIGNED |
| | AND INSTALLED TO RESIST THE WIND |
| | PRESSURES ON THE EQUIPMENT & THE |
| | SUPPORTS AS DETERMINED IN ACCORDANCE |
| | WITH THE FL BLD CODE. THIS MAY BE ACCOMP |
| | LISHED BY DESIGN OR BY APPLICATION OF |
| | SECTION 301.13.1. |
| | |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |