Notes
Date Text
2005-01-21 00:00:00BUILDING PLAN REVIEW
 PERMIT:05010076
 ADD: 1400 NORTHPOINT PKWY# 10
 CONT: BRICAR ENTERPRISES
 TEL: (954)675-1976
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
  
 1)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 THE NEW LAB DOESN'T INDICATE IF THERE
 WILL BE FUME HOODS? WHAT QUANITIES OF
 GASSES WILL BE STORED?
  
 2) ALSO THE PLUMBING PAGES INDICATE THE
 USE OF HYDROGEN TANKS IN A INCLOSURE
 BUT THERE IS NO MENTION OF PIPING OF
 HYDROGEN?
  
 3)THE ENCLOSURE HOLDING THE HYDROGEN
 TANK WHAT IS IT RATED FOR?
  
 4) 1511.7 ROOF MOUNTED MECHANICAL UNITS
 SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
 MECH. 301.13 WIND RESISTANCE MECHANICAL
 EQUIPMENT, APPLIANCES AND SUP PORTS THAT
 ARE EXPOSED TO WIND SHALL BE DESIGNED
 AND INSTALLED TO RESIST THE WIND
 PRESSURES ON THE EQUIPMENT & THE
 SUPPORTS AS DETERMINED IN ACCORDANCE
 WITH THE FL BLD CODE. THIS MAY BE ACCOMP
 LISHED BY DESIGN OR BY APPLICATION OF
 SECTION 301.13.1.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026